| '''E''' - Fix it using DIN912 M3x8 screws; | | '''E''' - Fix it using DIN912 M3x8 screws; |
| + | |
| + | == Disclaimer == |
| + | |
| + | === RCD - residual current device === |
| + | Charger must be installed together with RCD Type B. |
| + | |
| + | In order to successfully use Teltocharge product, users electrical grid must include dedicated RCD Type B exclusively for it. RCD must be installed by experienced electrician, who installs it parallelly with the charger. Residual current device is not included into the package and have to be bought separately. Legitimate options: |
| + | |
| + | '''Installation option 1:''' |
| + | |
| + | Residual current protection (RCBO) type B with tripping current 30 mA and with 32 A overcurrent protection according to at least one of the standards IEC 61009-1 or IEC 60947-2. |
| + | |
| + | '''Installation option 2:''' |
| + | |
| + | Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61008-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection rated 32 A should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series. |
| + | |
| + | Before buying, please consult with the company, which installs the product. |
| + | |
| + | === SPD - surge protection device === |
| + | In order to successfully use Teltocharge product, users electrical grid must include dedicated Surge Protective Device (SPD in short) exclusively for it. SPD must be installed by experienced electrician, who installs it parallelly with the charger. |
| + | |
| + | Surge protective device is not included into the package and have to be bought separately. Legitimate options: |
| + | |
| + | '''Installation option 1:''' |
| + | |
| + | Surge protective device (SPD) type 1 with max continuous working voltage = 275VAC and maximum transient voltage tolerance of 2500 V. Device must be certified according to the standard IEC 61643 - 11. |
| + | |
| + | '''Installation option 2:''' |
| + | |
| + | Surge protective device (SPD) combined type 1&2 with max continuous working voltage = 275VAC and maximum transient voltage tolerance of 2500 V. Device must be certified according to the standard IEC 61643 - 11. |
| + | |
| + | Before buying, please consult with the company, which installs the product. |
| | | |