= DYNAMIC LOAD BALANCING =
= DYNAMIC LOAD BALANCING =
TeltoCharge can communicate with a dedicated smart energy meter and adjust its power consumption based on the meter's readings. This functionality helps protect the home's electrical grid from overload during peak hours and optimizes energy usage to match the user's habits. The smart energy meter should always be installed in the main electrical cabinet, as shown below.
EVC2 can communicate with a dedicated smart energy meter and adjust its power consumption based on the meter's readings. This functionality helps protect the home's electrical grid from overload during peak hours and optimizes energy usage to match the user's habits. The smart energy meter should always be installed in the main electrical cabinet, as shown below.
[[File:Dynamic_Load_Balancing_Conection_Schematic.png|alt=|center|frameless|395x395px]]
[[File:Dynamic_Load_Balancing_Conection_Schematic.png|alt=|center|frameless|395x395px]]


Line 7: Line 7:
We can achieve DLB support by pairing the charger with one of the following:
We can achieve DLB support by pairing the charger with one of the following:


* [[Dynamic Load Balancing EVC2#SMART METER AND TELTOCHARGE COMMUNICATION|Energy meter]]
* [[Dynamic Load Balancing EVC2#MODBUS RTU METERS|Modbus RTU meters]]
* [[Dynamic Load Balancing EVC2#MODBUS TCP/IP METERS|Modbus TCP/IP meters]]
* [[Dynamic Load Balancing EVC2#CT CLAMPS|CT clamps]]
* [[Dynamic Load Balancing EVC2#CT CLAMPS|CT clamps]]
* [[Dynamic Load Balancing EVC2#EXTERNAL CONTROL|External control]]
* [[Dynamic Load Balancing EVC2#EXTERNAL CONTROL|External control (EMS)]]
* [[Dynamic Load Balancing EVC2#SMARTSTUFF P1 CONVERTER|Smartstuff P1 converter]]
* [[Dynamic Load Balancing EVC2#SMARTSTUFF P1 CONVERTER|Smartstuff P1 converter]]


Line 15: Line 16:


== PHASE BALANCE EXPLANATION ==
== PHASE BALANCE EXPLANATION ==
TeltoCharge has advanced functionality to detect a car's charging type and, if required, switch phases during mid-charge.
TeltoCharge has advanced functionality to detect a car's charging type and, if required, switch phases mid-charge.


The same phase switch process will happen if the smart meter detects, that less than 6A is available for one of the phases.
The same phase switch process will happen if the smart meter detects that less than 6A is available for one of the phases.


=== Adaptation to the car's charging capability ===
=== Adaptation to the car's charging capability ===
If the charger is set for 3phase charging, but the plugged car can only draw current from one phase, TeltoCharge will switch to one-phase mode after a short period of time
If the charger is set for 3phase charging, but the plugged car can only draw current from one phase, TeltoCharge will switch to one-phase mode after a short period of time.


[[File:CarExample.png|frameless|493x493px]]
[[File:CarExample.png|frameless|493x493px]]


=== Phase balance during lack of power ===
=== Phase balance during lack of power ===
When the smart meter detects that there is less than 6A for each phase, the charging station will switch from 3phase mode to 1phase mode until 6ampers are available for all phases
When the smart meter detects that there is less than 6A for each phase, the charging station will switch from 3phase mode to 1phase mode until 6ampers are available for all phases.


[[File:PhaseSwitch.png|frameless|600x600px]]
[[File:PhaseSwitch.png|frameless|600x600px]]


== SMART METER AND TELTOCHARGE COMMUNICATION ==
== MODBUS RTU METERS ==
Smart meter and TeltoCharge communicates via Modbus RS-485 protocol. In order to achieve smooth communication, it is recommended to use communication cable according to this protocol. Check example below.
To access energy measurement through Modbus RTU, connect both the charger and the meter together using RS485 terminal for meter.
 
[[File:DLB meter.png|frameless|808x808px]]
 
=== RS485 communication ===
For RS485 communication it is recommended to use a twister pair communication cable. Check example below.


[[File:TeltoCharge_DLB_CableExample.png|frameless]]
[[File:TeltoCharge_DLB_CableExample.png|frameless]]
Line 36: Line 42:
'''Note:''' ''Communication cable should be integrated with power cable.''
'''Note:''' ''Communication cable should be integrated with power cable.''


== SUPPORTED ENERGY METERS ==
In order to strive for wider applicability and compatibility, we constantly test and add new supported devices into list. All of the supported energy meters and schematics how to connect them are provided below.  
In order to strive for wider applicability and compatibility, we constantly test and add new supported devices into list. All of the supported Energy meters and schematics how to connect them are provided below.  


In order to make '''Dynamic load balancing''' and '''Solar''' functionality work, please always check:
In order to make '''Dynamic load balancing''' and '''Solar''' functionality work, please always check:


* if the '''wiring''' your Smart energy meter to TeltoCharge is right.
* if the '''wiring''' from your Smart energy meter to EVC2 is right.
* if the '''installer menu configuration''' in mobile application according to your Smart energy meter is right.
* if the '''installer menu configuration''' in mobile application according to your smart energy meter is right.


=== Supported Modbus RTU models ===
{| class="wikitable" style="text-align: center; border: 1px solid #dddddd; font-family: arial, sans-serif; width: 60%;"
{| class="wikitable" style="text-align: center; border: 1px solid #dddddd; font-family: arial, sans-serif; width: 60%;"
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" |Energy meter manufacturer
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" |Energy meter manufacturer
Line 78: Line 84:
| style="padding: 2px;" |[[Chint models]]
| style="padding: 2px;" |[[Chint models]]
| style="padding: 2px;" |[[Chint settings]]
| style="padding: 2px;" |[[Chint settings]]
| style="padding: 2px;" |[https://wiki.teltonika-energy.com/images/3/3b/Inepro_pro380.png METER -> TELTOCHARGE]  
| style="padding: 2px;" |[https://wiki.teltonika-energy.com/images/7/7e/Chint_meter_%281%29.png METER -> TELTOCHARGE]  
|-
|-
| style="padding: 2px;" |Entes  
| style="padding: 2px;" |Entes  
Line 91: Line 97:
|-
|-
| colspan="4" style="padding: 8px;" |''More coming soon...''
| colspan="4" style="padding: 8px;" |''More coming soon...''
|}
== LOAD BALANCING CONFIGURATION ==
To ensure everything works correctly, please apply the following setup :
# Open user menu
# Open "'''''Installer Menu'''''"
# Open "'''''Dynamic Load Balancing'''''" menu
# Enable "'''''Load Balancing'''''"
# If smart meter is connected with RS485 wires, press "'''''Search For Device'''''"
# *'''ONLY If TeltoCharge is unable''' to identify energy meter - use "'''''Manual Setup'''''"
[[File:DLB_settings.png|frameless|989x989px]]
== MODBUS TCP/IP METERS ==
To access energy measurement through Modbus TCP/IP, connect both the meter and your charger to your network. Charger has two options: either Wi-Fi or Ethernet cable.
=== Connecting Shelly 3PRO ===
Download the '''Shelly smart control''' app and setup the device to connect to your network. After it is configured, find the IP address given to the meter.
[[File:Shelly wiki.png|frameless|935x935px]]
'''''Note:''' Copy the IP as it will be used in EV charging app to connect the meter to the station''
=== Connecting HomeWizard P1 ===
Follow this full guide for easy installation: [[Media:HomeWizard P1 guide.pdf|HomeWizard P1.pdf]]
Or in short - install the HomeWizard meter to the P1 port of your utility meter.
[[File:Wizard p1 utility meter.png|frameless|284x284px]]
Download the '''HomeWizard''' app and follow the setup for the meter to connect to your network. After it is configured, find the IP address given to the meter.
[[File:Homewizard wiki 1.png|frameless]] [[File:Homewizard wiki 3.png|frameless|592x592px]]
'''''Note:''' Copy the IP as it will be used in EV charging app to connect the meter to the station''
=== Load balancing using Network meter ===
The example below is for Shelly 3Pro smart meter integration, but is identical when using HomeWizard P1.
To connect the meter to the station, go to '''load balancing''' section in the app, choose '''network meter''' and the model you're using.
[[File:Shelly DLB 1.png|frameless|938x938px]]
After that select the '''IP address''' as was shown in the Shelly app. Set '''max grid load''' to match the value allowed by the grid. If everything is done right - the status should indicate that the network meter has successfully connected.
[[File:Shelly DLB 2.png|937x937px]]
=== Supported Modbus TCP/IP models ===
{| class="wikitable" style="text-align: center; border: 1px solid #dddddd; font-family: arial, sans-serif; width: 60%;"
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" |Energy meter manufacturer
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" |Technical information
|-
|-
| style="padding: 2px;" |Shelly
| style="padding: 2px;" |3em models
|-
| style="padding: 2px;" |Homewizard
| style="padding: 2px;" |P1 models
|-
|Eastron
|SEM
|}
|}


== CT CLAMPS ==
== CT CLAMPS ==
It is possible to measure power readings by connecting CT clamps to each phase. Insert each CT clamp to its dedicated terminal (blue wire to B, red wire to R slot of the terminal).
It is possible to measure power readings by connecting CT clamps to each phase. Insert each CT clamp to its dedicated terminal (blue wire to B, red wire to A slot of the terminal).


<u>Make sure that clamp direction is pointing towards source (away from the charger).</u>
<u>Make sure that clamp direction is pointing towards source (away from the charger).</u>
[[File:CT clamps EVC2.png|frameless|529x529px]]
[[File:CT clamps EVC2.png|frameless|529x529px]]


 
<big>'''Mandatory CT clamp specifications:'''
Recommended CT clamp specifications:
</big>
 
* Rated input/current - depends on your total power input, but we would recommend not to exceed 150A.
* Rated input/current - depends on your total power input, but we would recommend not to exceed 150A.
* Turn ratio - 3000:1.
* Turn ratio - 3000:1.
Line 120: Line 185:


# It can be configured to use a watchdog for communication and if no valid communication is present after a configurable time interval, the charging (if ongoing) will stop and EVSE will not perform any charging until valid communication is reestablished;
# It can be configured to use a watchdog for communication and if no valid communication is present after a configurable time interval, the charging (if ongoing) will stop and EVSE will not perform any charging until valid communication is reestablished;
# the EVSE does not use a watchdog and continuous communication is not needed. As it is possible to change the EVSE settings by using the TeltoCharge mobile application, it is recommended for the primary device to read, compare, and change settings as needed based on user preferences and real-time requirements, ensuring a seamless and secure charging experience for electric vehicle owners. Continuous monitoring and adjustment of EVSE settings enable the primary device to stay synchronized with user inputs, maintain optimal charging conditions, and promptly respond to any changes initiated through the TeltoCharge mobile application, thereby enhancing overall efficiency and user satisfaction.
# The EVSE does not use a watchdog and continuous communication is not needed. As it is possible to change the EVSE settings by using the TeltoCharge mobile application, it is recommended for the primary device to read, compare, and change settings as needed based on user preferences and real-time requirements, ensuring a seamless and secure charging experience for electric vehicle owners. Continuous monitoring and adjustment of EVSE settings enable the primary device to stay synchronized with user inputs, maintain optimal charging conditions, and promptly respond to any changes initiated through the TeltoCharge mobile application, thereby enhancing overall efficiency and user satisfaction.


=== Device preparation ===
=== Device preparation ===
TeltoCharge must be configured as a secondary device via a TeltoCharge mobile application and device must have RS485 wired connection with the primary device..
TeltoCharge must be configured as a secondary device via a TeltoCharge mobile application and must have a RS485 wired connection with the primary device..


# Open "User menu"
# Open "User menu"
Line 170: Line 235:
| -
| -
|V
|V
|Input voltage on L2
|Input voltage on L3
|-
|-
|3
|3
Line 266: Line 331:
|'''Phase connected'''
|'''Phase connected'''
|uint16
|uint16
|0-6
|0-7
| -
| -
| -
| -
Line 295: Line 360:
|'''Request stop charging'''
|'''Request stop charging'''
|uint16
|uint16
|0-1
|0-2
| -
| -
| -
| -
|Request stop charging
|Do not intervene with current session (0), stop session (1) or start session if stopped (2).
|-
|-
|17
|17
Line 367: Line 432:
|R
|R
|'''Serial number 1st word'''
|'''Serial number 1st word'''
|
|uint16
|0-65535
|0-65535
|123456789
|123456789
Line 376: Line 441:
|R
|R
|'''Serial number 2nd word'''
|'''Serial number 2nd word'''
|
|uint16
|0-65535
|0-65535
|
|
Line 406: Line 471:
|6-1000
|6-1000
|30
|30
| -
| A
|Defines max power from grid
|Defines max power from grid
|-
|-
Line 415: Line 480:
|6-32
|6-32
|10
|10
| -
| A
|Defines max settable current by user
|Defines max settable current by user
|-
|-
Line 478: Line 543:
|'''Current limit cause'''
|'''Current limit cause'''
|uint16
|uint16
|0-8
|0-7
| -
| -
| -
| -
Line 555: Line 620:
|*100kWh
|*100kWh
|Total supplied active power in a lifetime (uint16_t) >> 48
|Total supplied active power in a lifetime (uint16_t) >> 48
|-
|45
|R/W
|'''Max. limit of random delay'''
|uint16
|1-1800
|600
|s
|Max. limit of the randomized delay in seconds
|}
|}
{| class="wikitable"
{| class="wikitable"
Line 674: Line 748:


== SMARTSTUFF P1 CONVERTER ==
== SMARTSTUFF P1 CONVERTER ==
The Modbus P1 Dongle is a device that enables communication between your TeltoCharge EV charging station and a smart meter using the Modbus RS-485 protocol. This setup is essential for accurately monitoring and controlling the energy usage during EV charging sessions.
The Modbus P1 Dongle is a device that enables communication between your EVC charging station and a smart meter using the Modbus RS-485 protocol. This setup is essential for accurately monitoring and controlling the energy usage during EV charging sessions.


* Accurate energy monitoring: Ensures that energy usage data is correctly captured and transmitted.
* Accurate energy monitoring: Ensures that energy usage data is correctly captured and transmitted.
Line 685: Line 759:


=== RS-485 Connection ===
=== RS-485 Connection ===
The dongle features RS-485 terminals which are critical for establishing communication with the TeltoCharge system. These terminals are usually labeled as Ground (GND), A+ (positive differential signal), and B- (negative differential signal).
The dongle features RS-485 terminals which are critical for establishing communication with the EVC2 system. These terminals are usually labeled as Ground (GND), A+ (positive differential signal), and B- (negative differential signal).


* To connect the dongle to the TeltoCharge, you'll need to use an appropriate RS-485 cable.
* To connect the dongle to the EVC2, you'll need to use an appropriate RS-485 cable.
* Connect the 'A+' terminal of your cable to the 'A+' port on the TeltoCharge device.
* Connect the 'A+' terminal of your cable to the 'A+' port on the EVC2 device.
* Connect the 'B-' terminal of your cable to the 'B-' port on the TeltoCharge device.
* Connect the 'B-' terminal of your cable to the 'B-' port on the EVC2 device.


''Note :'' In case of communication errors, swapping the 'A+' and 'B-' connections might resolve the issue.
''Note :'' In case of communication errors, swapping the 'A+' and 'B-' connections might resolve the issue


[[File:Modbus_p1_dongle_-rs485.png|alt=|frameless|400x400px]]<blockquote>'''''https://smart-stuff.nl/contact/'''''</blockquote>
.        [[File:EVC2 p1 LB.png|frameless|801x801px]]<blockquote>https://docs.smart-stuff.nl/p1-modbus-dongle/quick-start/installation</blockquote>


=== General meter settings ===
=== General meter settings ===
According to your smart meter documentation, please enter all the settings into the Teltonika app as shown.
According to your smart meter documentation, please enter all the settings into the Energy app as shown.


# '''Energy meter type''': You need to select the type of smart meter (1-phase/3-phase). Please note that you can use a 1-phase charger even if the meter is 3-phase.
# '''Energy meter type''': You need to select the type of smart meter (1-phase/3-phase). Please note that you can use a 1-phase charger even if the meter is 3-phase.
Line 737: Line 811:
# *'''ONLY If TeltoCharge is unable''' to identify energy meter - use "'''''Manual Setup'''''"
# *'''ONLY If TeltoCharge is unable''' to identify energy meter - use "'''''Manual Setup'''''"


[[File:DLB_settings.png|frameless|900x900px]]  
[[File:DLB_settings.png|frameless|1062x1062px]]  