Changes

Line 14: Line 14:     
[[File:MicrosoftTeams-image (33).png|alt=|frameless|left|[[File:Ct-meter.png|thumb]]]]
 
[[File:MicrosoftTeams-image (33).png|alt=|frameless|left|[[File:Ct-meter.png|thumb]]]]
[[File:Ct-direction.jpeg|frameless|371x371px|alt=|right]] [[File:Ct-meter.png|frameless|331x331px|alt=|center]]
+
[[File:Ct-direction.jpeg|frameless|371x371px|alt=|right]] [[File:Ct-meter.png|frameless|331x331px|alt=|center]]Note : The CT cable included in the box is 3 meters long. Users can extend it to their desired length, depending on installation conditions such as electrical noise and resistance. However, we recommend not using an extension longer than 100 meters.
    
===DLM with smart meter:===
 
===DLM with smart meter:===
Line 27: Line 27:     
[[File:DLM without meter.png|center|frameless|776x776px]]
 
[[File:DLM without meter.png|center|frameless|776x776px]]
 +
 +
Note : The CT cable included in the box is 3 meters long. Users can extend it to their desired length, depending on installation conditions such as electrical noise and resistance. However, we recommend not using an extension longer than 100 meters.
 +
    
==Teltonika Energy App Settings==
 
==Teltonika Energy App Settings==
 
Once the chargers are properly connected to the electrical grid and interconnected to each other, the next step is to configure the settings for each charger using the Teltonika Energy app. Below, you will find a comprehensive list of the settings that should be adjusted to achieve DLM functionality.
 
Once the chargers are properly connected to the electrical grid and interconnected to each other, the next step is to configure the settings for each charger using the Teltonika Energy app. Below, you will find a comprehensive list of the settings that should be adjusted to achieve DLM functionality.
   −
=== Max power from grid===
+
===Max power from grid===
 
[[File:2023-07-03 07 42 32-Window.png|right|frameless|245x245px]]
 
[[File:2023-07-03 07 42 32-Window.png|right|frameless|245x245px]]
 
It is very important to set this parameter correctly in the master charger if you want to use DLM. This parameter shows how much of current you have in the circuit you want to balance. That means you have to set as much as this current can have amperes. Usually it should be the same current as the breaker tripping current. If for example in the master charger you will set lower current, DLM might not work and charger might not even start charging process.
 
It is very important to set this parameter correctly in the master charger if you want to use DLM. This parameter shows how much of current you have in the circuit you want to balance. That means you have to set as much as this current can have amperes. Usually it should be the same current as the breaker tripping current. If for example in the master charger you will set lower current, DLM might not work and charger might not even start charging process.
Line 48: Line 51:  
These settings must be configured for all chargers in the circuit, regardless of whether they are slaves and have direct communication with the meter. These settings establish the communication protocol between the master-slave and master-meter.
 
These settings must be configured for all chargers in the circuit, regardless of whether they are slaves and have direct communication with the meter. These settings establish the communication protocol between the master-slave and master-meter.
   −
===General CT settings===
+
=== General CT settings===
 
[[File:Calibrate-ct.jpg|right|frameless|266x266px|link=Special:FilePath/Calibrate-ct.jpg]]
 
[[File:Calibrate-ct.jpg|right|frameless|266x266px|link=Special:FilePath/Calibrate-ct.jpg]]
 
1- By default, it is set to 3 seconds. However, there may be cases where the user needs to increase this value. For instance, if there are significant distances between the chargers and the ct clamps or if there are numerous interconnected chargers.
 
1- By default, it is set to 3 seconds. However, there may be cases where the user needs to increase this value. For instance, if there are significant distances between the chargers and the ct clamps or if there are numerous interconnected chargers.
Line 70: Line 73:  
#'''Current update interval''': By default, it is set to 3 seconds. However, there may be cases where the user needs to increase this value. For instance, if there are significant distances between the chargers and the smart meter or if there are numerous interconnected chargers.
 
#'''Current update interval''': By default, it is set to 3 seconds. However, there may be cases where the user needs to increase this value. For instance, if there are significant distances between the chargers and the smart meter or if there are numerous interconnected chargers.
   −
=== Dynamic Load Management===
+
===Dynamic Load Management===
 
When setting up all the previous configurations, it is time to proceed with the main DLM settings. To enable these settings, the user must first activate DLM.
 
When setting up all the previous configurations, it is time to proceed with the main DLM settings. To enable these settings, the user must first activate DLM.
 
[[File:Dlm.png|right|frameless|292x292px]]
 
[[File:Dlm.png|right|frameless|292x292px]]
Line 79: Line 82:  
#*Distribution by priority: Energy will be distributed based on priority. Chargers will be prioritized according to their charging state, and those with higher priority will receive maximum charging power.[[File:Dlm.png|right|frameless|276x276px]]''For example, if we have a 100 A grid and five connected chargers, each capable of accepting 30 A, the first three chargers will receive 30 A each. The fourth charger will receive only 10 A, and the fifth charger will not initiate the charging process at all. This setting is exclusive to the master charger.''
 
#*Distribution by priority: Energy will be distributed based on priority. Chargers will be prioritized according to their charging state, and those with higher priority will receive maximum charging power.[[File:Dlm.png|right|frameless|276x276px]]''For example, if we have a 100 A grid and five connected chargers, each capable of accepting 30 A, the first three chargers will receive 30 A each. The fourth charger will receive only 10 A, and the fifth charger will not initiate the charging process at all. This setting is exclusive to the master charger.''
 
#'''Slave Modbus address start''' - This setting is exclusive to the master charger. The user needs to specify the starting address for the slave chargers. For instance, if the start address is set to 1, the first slave charger should have address 1, the second should have address 2, the third should have address 3, and so on.
 
#'''Slave Modbus address start''' - This setting is exclusive to the master charger. The user needs to specify the starting address for the slave chargers. For instance, if the start address is set to 1, the first slave charger should have address 1, the second should have address 2, the third should have address 3, and so on.
# Each slave charger has its own specific setting called "'''Slave Modbus address'''". This setting must be configured individually for each charger.
+
#Each slave charger has its own specific setting called "'''Slave Modbus address'''". This setting must be configured individually for each charger.
 
#'''Number of devices''' - This setting is available only for the master charger. The administrator must specify the total number of slave chargers that will be connected in the circuit.
 
#'''Number of devices''' - This setting is available only for the master charger. The administrator must specify the total number of slave chargers that will be connected in the circuit.

Navigation menu