Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61009-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection (MCB) rated for atleast 32 A (it is recommended to use 40 A) should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series.  
 
Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61009-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection (MCB) rated for atleast 32 A (it is recommended to use 40 A) should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series.  
 +
 +
'''Installation option 3:'''
 +
RCD Type A and appropriate equipment that ensures the disconnection of the supply in case of DC fault current above 6 mA. DC disconnection equipment must meet IEC 62955 standard requirements.
    
Before buying, please consult with the company, which installs the product.
 
Before buying, please consult with the company, which installs the product.
   −
'''Installation option 3:'''
  −
RCD Type A and appropriate equipment that ensures the disconnection of the supply in case of DC fault current above 6 mA. DC disconnection equipment must meet IEC 62955 standard requirements.
      
=== SPD - surge protection device ===
 
=== SPD - surge protection device ===