Difference between revisions of "11 kW TeltoCharge Suggested configuration"

From Wiki
 
(One intermediate revision by the same user not shown)
Line 6: Line 6:
 
   <ul style="list-style-type: none; margin: 0; padding: 0;">
 
   <ul style="list-style-type: none; margin: 0; padding: 0;">
 
<br>
 
<br>
To run your 11 kW TeltoCharge on 1 phase, please follow this link to suggested parameters: [[7.4 kW TeltoCharge Suggested configuration]]. With 1-phase of 11 kW TeltoCharge you can achieve to charge at maximum 7.4 kW power.
+
To run your 11 kW TeltoCharge on 1 phase, please follow this table below with suggested configurations. With 1-phase of 11 kW TeltoCharge you can achieve to charge at maximum 3.7 kW power.
 +
 
 +
{| class="wikitable" style="text-align: center; border: 1px solid #0054A6; font-family: arial, sans-serif; width: 60%;"
 +
|-
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Option number in installer
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Installer menu parameter name
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 4px;" | Suggested value to set
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Link to description of parameter
 +
|-
 +
| style="padding: 8px;" | 01
 +
| style="padding: 8px;" | '''Max power from grid'''
 +
| style="padding: 8px;" | 16 A
 +
| style="padding: 8px;" | [[Max power from grid]]
 +
|-
 +
| style="padding: 8px;" | 02
 +
| style="padding: 8px;" | '''Supply voltage '''
 +
| style="padding: 20px;" | 230 V
 +
| style="padding: 8px;" | [[Supply voltage]]
 +
|-
 +
| style="padding: 8px;" | 03
 +
| style="padding: 8px;" | '''Upper voltage tolerance'''
 +
| style="padding: 8px;" | 10 %
 +
| style="padding: 8px;" | [[Upper voltage tolerance]]
 +
 
 +
|-
 +
| style="padding: 8px;" | 04
 +
| style="padding: 8px;" | '''Lower voltage tolerance'''
 +
| style="padding: 8px;" | 10 %
 +
| style="padding: 8px;" | [[Lower voltage tolerance]]
 +
|-
 +
| style="padding: 8px;" | 05
 +
| style="padding: 8px;" | '''Three phase charging'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Three phase charging]]
 +
|-
 +
| style="padding: 8px;" | 06
 +
| style="padding: 8px;" | '''Phase priority'''
 +
| style="padding: 8px;" | L1
 +
| style="padding: 8px;" | [[Phase priority]]
 +
|-
 +
| style="padding: 8px;" | 07
 +
| style="padding: 8px;" | '''Difference between phases'''
 +
| style="padding: 8px;" | 120 °
 +
| style="padding: 8px;" | [[Difference between phases]]
 +
|-
 +
| style="padding: 8px;" | 08
 +
| style="padding: 8px;" | '''Use neutral as phase'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Use neutral as phase]]
 +
|-
 +
| style="padding: 8px;" | 09
 +
| style="padding: 8px;" | '''Use data from energy meter'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Use data from energy meter]]
 +
|-
 +
| style="padding: 8px;" | 10
 +
| style="padding: 8px;" | '''kWh meter address'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.''
 +
| style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 +
|-
 +
| style="padding: 8px;" | 11
 +
| style="padding: 8px;" | '''Energy meter type'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 12
 +
| style="padding: 8px;" | '''RS-485 baudrate'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 13
 +
| style="padding: 8px;" | '''RS-485 parity'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 14
 +
| style="padding: 8px;" | '''RS-485 stop bit'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 15
 +
| style="padding: 8px;" | '''Dynamic load balancing'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Dynamic Load Balancing]]
 +
|-
 +
| style="padding: 8px;" | 16
 +
| style="padding: 8px;" | '''Use preferred phase'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.'''
 +
| style="padding: 8px;" | [[Use prefered phase]]
 +
|-
 +
| style="padding: 8px;" | 17
 +
| style="padding: 8px;" | '''Energy meter address'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 +
|-
 +
| style="padding: 8px;" | 18
 +
| style="padding: 8px;" | '''Allow simplified charging sequence'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Allow simplified charging sequence]]
 +
|-
 +
| style="padding: 8px;" | 19
 +
| style="padding: 8px;" | '''Charger location is ventilated'''
 +
| style="padding: 8px;" | OFF (if your TeltoCharge is inside the property)
 +
| style="padding: 8px;" | [[Charger location is ventilated]]
 +
|-
 +
| style="padding: 8px;" | 20
 +
| style="padding: 8px;" | '''Temperature warning'''
 +
| style="padding: 8px;" | 60 °C
 +
| style="padding: 8px;" | [[Temperature warning]]
 +
|}
 +
 
 
   <h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">3 phase (3L+N+PE) | voltage between L-N 230V ± 10% | L-L 400V ± 10%</h2>
 
   <h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">3 phase (3L+N+PE) | voltage between L-N 230V ± 10% | L-L 400V ± 10%</h2>
 
   <ul style="list-style-type: none; margin: 0; padding: 0;">
 
   <ul style="list-style-type: none; margin: 0; padding: 0;">
Line 36: Line 142:
 
| style="padding: 8px;" | 10 %
 
| style="padding: 8px;" | 10 %
 
| style="padding: 8px;" | [[Upper voltage tolerance]]
 
| style="padding: 8px;" | [[Upper voltage tolerance]]
 
 
|-
 
|-
 
| style="padding: 8px;" | 04
 
| style="padding: 8px;" | 04
Line 42: Line 147:
 
| style="padding: 8px;" | 10 %
 
| style="padding: 8px;" | 10 %
 
| style="padding: 8px;" | [[Lower voltage tolerance]]
 
| style="padding: 8px;" | [[Lower voltage tolerance]]
 
 
|-
 
|-
 
| style="padding: 8px;" | 05
 
| style="padding: 8px;" | 05
 +
| style="padding: 8px;" | '''Three phase charging'''
 +
| style="padding: 8px;" | ON
 +
| style="padding: 8px;" | [[Three phase charging]]
 +
|-
 +
| style="padding: 8px;" | 06
 
| style="padding: 8px;" | '''Phase priority'''
 
| style="padding: 8px;" | '''Phase priority'''
 
| style="padding: 8px;" | L1
 
| style="padding: 8px;" | L1
 
| style="padding: 8px;" | [[Phase priority]]
 
| style="padding: 8px;" | [[Phase priority]]
 
|-
 
|-
| style="padding: 8px;" | 06
+
| style="padding: 8px;" | 07
 
| style="padding: 8px;" | '''Difference between phases'''
 
| style="padding: 8px;" | '''Difference between phases'''
 
| style="padding: 8px;" | 120 °
 
| style="padding: 8px;" | 120 °
 
| style="padding: 8px;" | [[Difference between phases]]
 
| style="padding: 8px;" | [[Difference between phases]]
 
|-
 
|-
| style="padding: 8px;" | 07
+
| style="padding: 8px;" | 08
 
| style="padding: 8px;" | '''Use neutral as phase'''
 
| style="padding: 8px;" | '''Use neutral as phase'''
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | [[Use neutral as phase]]
 
| style="padding: 8px;" | [[Use neutral as phase]]
 
|-
 
|-
| style="padding: 8px;" | 08
+
| style="padding: 8px;" | 09
 
| style="padding: 8px;" | '''Use data from energy meter'''
 
| style="padding: 8px;" | '''Use data from energy meter'''
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | [[Use data from energy meter]]
 
| style="padding: 8px;" | [[Use data from energy meter]]
 
|-
 
|-
| style="padding: 8px;" | 09
+
| style="padding: 8px;" | 10
 
| style="padding: 8px;" | '''kWh meter address'''
 
| style="padding: 8px;" | '''kWh meter address'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.''
 
| style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 
| style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 
|-
 
|-
| style="padding: 8px;" | 10
+
| style="padding: 8px;" | 11
 
| style="padding: 8px;" | '''Energy meter type'''
 
| style="padding: 8px;" | '''Energy meter type'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
|-
 
|-
|-
+
| style="padding: 8px;" | 12
| style="padding: 8px;" | 11
 
 
| style="padding: 8px;" | '''RS-485 baudrate'''
 
| style="padding: 8px;" | '''RS-485 baudrate'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
|-
 
|-
| style="padding: 8px;" | 12
+
| style="padding: 8px;" | 13
 
| style="padding: 8px;" | '''RS-485 parity'''
 
| style="padding: 8px;" | '''RS-485 parity'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
|-
 
|-
| style="padding: 8px;" | 13
+
| style="padding: 8px;" | 14
 
| style="padding: 8px;" | '''RS-485 stop bit'''
 
| style="padding: 8px;" | '''RS-485 stop bit'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
|-
 
|-
| style="padding: 8px;" | 14
+
| style="padding: 8px;" | 15
 
| style="padding: 8px;" | '''Dynamic load balancing'''
 
| style="padding: 8px;" | '''Dynamic load balancing'''
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | [[Dynamic Load Balancing]]
 
| style="padding: 8px;" | [[Dynamic Load Balancing]]
 
|-
 
|-
| style="padding: 8px;" | 15
+
| style="padding: 8px;" | 16
 
| style="padding: 8px;" | '''Use preferred phase'''
 
| style="padding: 8px;" | '''Use preferred phase'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.'''
 
| style="padding: 8px;" | [[Use prefered phase]]
 
| style="padding: 8px;" | [[Use prefered phase]]
 
|-
 
|-
| style="padding: 8px;" | 16
+
| style="padding: 8px;" | 17
 
| style="padding: 8px;" | '''Energy meter address'''
 
| style="padding: 8px;" | '''Energy meter address'''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 
|-
 
|-
| style="padding: 8px;" | 17
+
| style="padding: 8px;" | 18
 
| style="padding: 8px;" | '''Allow simplified charging sequence'''
 
| style="padding: 8px;" | '''Allow simplified charging sequence'''
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | OFF
 
| style="padding: 8px;" | [[Allow simplified charging sequence]]
 
| style="padding: 8px;" | [[Allow simplified charging sequence]]
 
|-
 
|-
| style="padding: 8px;" | 18
+
| style="padding: 8px;" | 19
 
| style="padding: 8px;" | '''Charger location is ventilated'''
 
| style="padding: 8px;" | '''Charger location is ventilated'''
 
| style="padding: 8px;" | OFF (if your TeltoCharge is inside the property)
 
| style="padding: 8px;" | OFF (if your TeltoCharge is inside the property)
 
| style="padding: 8px;" | [[Charger location is ventilated]]
 
| style="padding: 8px;" | [[Charger location is ventilated]]
 
|-
 
|-
| style="padding: 8px;" | 19
+
| style="padding: 8px;" | 20
 
| style="padding: 8px;" | '''Temperature warning'''
 
| style="padding: 8px;" | '''Temperature warning'''
 
| style="padding: 8px;" | 60 °C
 
| style="padding: 8px;" | 60 °C
 
| style="padding: 8px;" | [[Temperature warning]]
 
| style="padding: 8px;" | [[Temperature warning]]
 
|}
 
|}

Latest revision as of 06:43, 30 May 2023

Introduction

    Here you can find information about Suggested configuration of 11 kW power TeltoCharge installer menu parameters according to your electrical grid.

    1 phase (1L+N+PE) | voltage between L-N 230V ± 10%