EVC2 RCBO
Appearance
RCBO device
An RCBO (Residual Current Circuit Breaker with Overcurrent protection) is a single electrical safety device that combines the functions of a Residual Current Device (RCD) and a Miniature Circuit Breaker (MCB). It protects circuits from two types of electrical faults: earth leakage currents (which RCDs protect against) and overcurrents (like overloads and short circuits, which MCBs protect against). If the household already does not posses a seperate RCD, this device allows to speed up the charger installation with a combined device to safely operate the EV charger. 1 phase and 3 phase versions available.
Datasheet
Certificates
Technical data
| Standard | IEC/EN61009-1 | ||
| Protection | Ground fault, Overcurrent and short circuit | ||
| Type of trip | Ground fault: Electronic | ||
| Overload and short circuit: Thermo-magnetic | |||
| Type of protection (electric leakage) | AC, A, S | ||
| No. of poles | 1P+N 3module, 3P+N 5 module, N line with disconnected | ||
| Rated current In | 6,10,16,20,25,32,40,50,63A | ||
| Rated voltage Ue | 1P+N:230/240V~, 3P+N:400/415V~ | ||
| Rated frequency | 50/60Hz | ||
| Rated sensitivity currents I△n | 10,30,100,300mA | ||
| Residual current off-time under I△n | ≤0.1s | ||
| Rated residual making and breaking capacity(I△m) | 500A(In≤50A),10In (In>50A) | ||
| Rated breaking capacity | EKL5-63: 6,000A, EKL5-63H: 10,000A | ||
| Energy limiting class | 3 | ||
| Rated impulse withstand voltage (1.2/50) Uimp | 4,000V | ||
| Dielectric test voltage at ind. Freq. for 1min | 2kV | ||
| Thermal release characteristic | (1.13-1.45) x In | ||
| Magnetic release characteristic | B:(3-5) x In, C:(5-10) x In, D:(10-20) x In | ||
| Electrical life | 4,000 Cycles | ||
| Mechanical life | 10,000 Cycles | ||
| Contact position indicator | Yes | ||
| Ground fault indicator | Yes | ||
| Protection degree | IP20 | ||
| Ambient temperature | -25℃ to +55℃, Max.95% humidity | ||
| Terminal connection type | Cable/Pin-type busbar | ||
| Max. terminal size for cable | 25mm2 | ||
| Max. tightening torque | 2.5N.m | ||
| Installation | Mounting on 35mm DIN rail | ||
| Connection | From top | ||