'''Installation option 1:'''  
 
'''Installation option 1:'''  
   −
Residual current protection (RCBO) type B with tripping current 30 mA and with 32 A overcurrent protection according to at least one of the standards IEC 61009-1 or IEC 60947-2.
+
Residual current protection (RCBO) type B with tripping current 30 mA and with atleast 32 A overcurrent protection according to at least one of the standards IEC 61009-1 or IEC 60947-2.
    
'''Installation option 2:'''  
 
'''Installation option 2:'''  
   −
Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61008-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection rated 32 A should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series.  
+
Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61008-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection rated for atleast 32 A should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series.  
    
Before buying, please consult with the company, which installs the product.
 