EVC2 RCBO

From Teltonika Energy Wiki
Revision as of 08:56, 3 November 2025 by Benas.K (talk | contribs)

RCBO device

Datasheet

EKL-63 RCBO

Certificates

CE and CB

Technical data

Standard IEC/EN61009-1
Protection Ground fault, Overcurrent and short circuit
Type of trip Ground fault: Electronic
Overload and short circuit: Thermo-magnetic
Type of protection (electric leakage) AC, A, S
No. of poles 1P+N 3module, 3P+N 5 module, N line with disconnected
Rated current In 6,10,16,20,25,32,40,50,63A
Rated voltage Ue 1P+N:230/240V~, 3P+N:400/415V~
Rated frequency 50/60Hz
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤50A),10In (In>50A)
Rated breaking capacity EKL5-63: 6,000A, EKL5-63H: 10,000A
Energy limiting class 3
Rated impulse withstand voltage (1.2/50) Uimp 4,000V
Dielectric test voltage at ind. Freq. for 1min 2kV
Thermal release characteristic (1.13-1.45) x In
Magnetic release characteristic B:(3-5) x In, C:(5-10) x In, D:(10-20) x In
Electrical life 4,000 Cycles
Mechanical life 10,000 Cycles
Contact position indicator Yes
Ground fault indicator Yes
Protection degree IP20
Ambient temperature -25℃ to +55℃, Max.95% humidity
Terminal connection type Cable/Pin-type busbar
Max. terminal size for cable 25mm2
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top