Jump to content

EVC2 Modbus TCP meters: Difference between revisions

From Teltonika Energy Wiki
No edit summary
No edit summary
Line 35: Line 35:
=== User and safety guide ===
=== User and safety guide ===
[[Media:Shelly Pro 3EM multilingual printed user and safety guide.pdf|Shelly Pro 3EM user and safety guide]]
[[Media:Shelly Pro 3EM multilingual printed user and safety guide.pdf|Shelly Pro 3EM user and safety guide]]
=== Resources ===
[https://www.shelly.com/blogs/documentation/shelly-pro-3em?srsltid=AfmBOopPoEcc-LmzmIZMtuASYl7jvN4q449i6NRq6XhfFm3q_Oo8MCUt Manufacturers documentation page]
=== Certificates and conformity declarations ===
=== Certificates and conformity declarations ===



Revision as of 10:18, 3 November 2025

Modbus TCP meters

Shelly PRO-3EM

Wiring diagram

Pro-3EM-wiring-diagram
Pro-3EM-wiring-diagram
















User and safety guide

Shelly Pro 3EM user and safety guide

Resources

Manufacturers documentation page

Certificates and conformity declarations

EU

UK

AU and NZ

Technical data

Type Value
Physical
Size (HxWxD): 94x19x69 ±0.5 mm / 3.70x0.75x2.71 ±0.02 in
Weight: 62 ±1 g / 2.19 ±0.05 oz
Mounting: DIN rail
Screw terminals max torque: 0.4 Nm / 4.43 lbin
Conductor cross section: 0.5 to 2.5 mm² / 20 to 14 AWG (solid, stranded, and bootlace lugs)
Conductor stripped length: 6 to 7 mm / 0.24 to 0.28 in
Shell material: Plastic
Color: White
Environmental
Ambient temperature: -20 °C to 40 °C / -5 °F to 105 °F
Humidity: 30 % to 70 % RH
Max. altitude: 2000 m / 6562 ft
Electrical
Power supply voltage AC: 100 - 260 V, 50/60 Hz
Power supply voltage DC: N/A
Power consumption: < 3 W
External protection: Tripping characteristic B or C,

16A max. rated current,

min. 6 kA interrupting rating,

energy limiting class 3

Sensors, meters
Internal-temperature sensor: Yes
Voltmeters (RMS for each phase): 100 - 260 V
Voltmeters accuracy: ±1 %
Ammeters (RMS via CT for each phase and the Neutral): 0 - 120 A
Compatible CT CT 120A
Ammeters accuracy: ±1 % (2 - 120 A), ±2 % (1 - 2 A), ±5 % (0 - 1 A)
Power and energy meters:
  • Active and apparent power
  • Active and apparent energy
  • Power factor
  • Fundamental active and fundamental reactive energy
Channel-to-channel calibration minimum load 500 W per channel
No load threshold: 30 VA per channel
Measurement data storage: At least 60 days of 1 min data resolution
Data export:
  • CSV for PQ recorded values
  • JSON format export through RPC
Radio
RF band: 2400 - 2495 MHz
Max. RF power: <20 dBm
Wi-Fi protocol: 802.11 b/g/n
Wi-Fi Range: Up to 30 m / 100 ft indoors and 50 m / 160 ft outdoors

(Depends on local conditions)

Bluetooth Protocol: 4.2
Bluetooth Range: Up to 10 m / 33 ft indoors and 30 m / 100 ft outdoors

(Depends on local conditions)

MCU
CPU: ESP32-D0WDQ6
Flash: 16 MB
Firmware capabilities
Webhooks (URL actions): 20 with 5 URLs per hook
Scripting: Yes
MQTT: Yes
CoAP: No