Phase difference based on your grid. This parameter is used only for the power consumption (kWh) calculations. It can be 120° or 180°.
 
Phase difference based on your grid. This parameter is used only for the power consumption (kWh) calculations. It can be 120° or 180°.
 +
 +
120° - Star (Wye) and Delta;
 +
180° - Delta and split phase.
 +
 +
In the case of Europe, most Star (Wye) and Delta connections will have a phase difference of 120°. In North America, the phase shift can be 180° when split phase connection type is used or in the case of Delta connection with center tap on one leg.