D - Close the front plate and fix it with M3x8 screws. | D - Close the front plate and fix it with M3x8 screws. | ||
== Dynamic Load Balancing (DLB) == | |||
Dynamic Load Balancing (DLB) is achieved by monitoring the total electrical consumption of the building through a dedicated smart energy meter or CT clamps installed in the main electrical cabinet. Based on the real-time measurements provided by this meter, the charger automatically adjusts its charging power to ensure that the total household load does not exceed the available electrical capacity. | |||
This functionality protects the building’s electrical installation from overload during peak usage periods and optimizes energy consumption according to the user's habits. The smart energy meter or CT clamps must always be installed at the main power source in the electrical distribution cabinet, where they can measure the total incoming current of the installation. | |||
[[File:MicrosoftTeams-image (33).png|alt=|frameless|left|[[File:Ct-meter.png|thumb]]]] | |||
[[File:Ct-direction.jpeg|frameless|371x371px|alt=|right]] [[File:Ct-meter.png|frameless|331x331px|alt=|center]] | |||
'''Note :''' The CT cable included in the box is 3 meters long. | |||
* Users can extend it to their desired length, depending on installation conditions such as electrical noise and resistance. | |||
* Recommended extension length is up to 100 meters. | |||
Principal scheme of connection: | |||
[[File:DLB with CT.png|alt=|frameless|395x395px|center|[[File:DLB with CT.png|thumb]]]] | |||
<br> | |||
==PEN CT WIRING== | ==PEN CT WIRING== | ||
| Line 29: | Line 45: | ||
<br> | <br> | ||
{| class="wikitable" style="text-align: center; border: 1px solid # | {| class="wikitable" style="text-align: center; border: 1px solid #0061FC; font-family: arial, sans-serif; width: 80%;" | ||
|- | |- | ||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Step Number | ! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Step Number | ||
| Line 54: | Line 70: | ||
| style="padding: 8px;" | '''Configure your TeltoCharge''' | | style="padding: 8px;" | '''Configure your TeltoCharge''' | ||
| style="padding: 8px;" | Follow steps in device configuration guide and using Teltonika EV Charging app set parameters according to your site requirements. | | style="padding: 8px;" | Follow steps in device configuration guide and using Teltonika EV Charging app set parameters according to your site requirements. | ||
| style="padding: 8px;" | . | | style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Dynamic_Load_Management_EVC16#Teltonika_Energy_App_Settings Possible settings] | ||
|- | |- | ||
| Line 66: | Line 82: | ||
| style="padding: 8px;" | Once the device is connected to the internet, go to the "OCPP" tab in "Connectivity" window and connect the charger to the Powerverse App by entering this URL: '''wss://ocpp.powerverse.com:443/''' <br> ''note: Make sure your phone doesn't auto correct wss.'' | | style="padding: 8px;" | Once the device is connected to the internet, go to the "OCPP" tab in "Connectivity" window and connect the charger to the Powerverse App by entering this URL: '''wss://ocpp.powerverse.com:443/''' <br> ''note: Make sure your phone doesn't auto correct wss.'' | ||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/images/e/ef/OCPP.png Connect to OCPP] | | style="padding: 8px;" | [https://wiki.teltonika-energy.com/images/e/ef/OCPP.png Connect to OCPP] | ||
|- | |||
| style="padding: 8px;" | Additional | |||
| style="padding: 8px;" | '''LED indicators''' | |||
| style="padding: 8px;" | Meaning of TeltoCharge LED indicators. | |||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Troubleshooting_Guide#LED_indicators LED indicators] | |||
|- | |||
|} | |||
==Configuration Setup Possibilities== | |||
===Home Installation Configuration with DLB and CT Clamps=== | |||
{| class="wikitable" style="text-align: center; border: 1px solid #0054A6; font-family: arial, sans-serif; width: 80%;" | |||
|- | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Step Number | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Description | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Suggestions | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Links | |||
|- | |||
| style="padding: 8px;" | 1 | |||
| style="padding: 8px;" | '''Make sure CT clamps are mounted correctly.''' | |||
| style="padding: 20px;" | You can check correct CT clamps installation option in this page above. | |||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/images/8/88/DLB_with_CT.png CT Scheme] | |||
|- | |||
| style="padding: 8px;" | 2 | |||
| style="padding: 8px;" | '''Go to Installer Settings via EV Charging APP''' | |||
| style="padding: 20px;" | Enter full 9-digit installer code to access installer menu. | |||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/images/0/06/Installer_menu_access.png Installer menu access] | |||
|- | |||
| style="padding: 8px;" | 3 | |||
| style="padding: 8px;" | '''Go to Installation section''' | |||
| style="padding: 8px;" | Set '''Max power from grid''' in amps according to your main circuit breaker value. | |||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/images/b/b1/Installation_section.png Installation section access] | |||
|- | |||
| style="padding: 8px;" | 4 | |||
| style="padding: 8px;" | '''Go to Load Balancing section''' | |||
| style="padding: 8px;" | 1. Select CT Clamp as measuring device. <br> 2. Enable Load Balancing and press on ''DLB CT'' button. <br> ''(Before calibration, ensure at least one CT is connected to the device and that its measuring end is not clamped around the cable)'' <br> 3. Calibrate your CT clamp. | |||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/images/5/57/Load_Balancing_CT_Calibration.png How to calibrate CT clamp] | |||
|- | |||
| style="padding: 8px;" | 5 | |||
| style="padding: 8px;" | '''Test setup''' | |||
| style="padding: 8px;" | 1. Plug in cable from charger to EV, but don't start charging. <br> 2. Go to '''Diagnostics''' window in the app and check if '''Max allowed current''' is more than at least 6 A to start charging. | |||
| style="padding: 8px;" | 1. [https://wiki.teltonika-energy.com/images/0/00/No_limitations_Diagnostics.png No limitations] <br> 2. [https://wiki.teltonika-energy.com/images/d/d1/Load_balance_limitations_Diagnostics.png Load balance limitations] | |||
|- | |- | ||
|} | |} | ||
Latest revision as of 16:21, 13 March 2026
Physical Device Installation Guide
INSTALLATION MANUAL
Press on the picture:

MAIN STEPS
A - Fix the device on the wall by inserting the self-tapping screws (start with the top screw and make sure the housing is horizontal).
B - Make sure the cable gland is properly mounted on the cables (AC input cable and Ethernet cable).
C - Close middle panel by placing it on the housing (the panel must click to the housing). And fix it using M3x8 screws.
D - Close the front plate and fix it with M3x8 screws.
Dynamic Load Balancing (DLB)
Dynamic Load Balancing (DLB) is achieved by monitoring the total electrical consumption of the building through a dedicated smart energy meter or CT clamps installed in the main electrical cabinet. Based on the real-time measurements provided by this meter, the charger automatically adjusts its charging power to ensure that the total household load does not exceed the available electrical capacity.
This functionality protects the building’s electrical installation from overload during peak usage periods and optimizes energy consumption according to the user's habits. The smart energy meter or CT clamps must always be installed at the main power source in the electrical distribution cabinet, where they can measure the total incoming current of the installation.




Note : The CT cable included in the box is 3 meters long.
- Users can extend it to their desired length, depending on installation conditions such as electrical noise and resistance.
- Recommended extension length is up to 100 meters.
Principal scheme of connection:


PEN CT WIRING
Product has integrated PEN fault protection.
In order to receive this functionality it is required to pass the PE cable through the internal current transformer. CT shall be wired in terminal marked "PEN".
Device Commissioning Guide
First Start Guide
Follow these detailed steps to get started with TeltoCharge in a correct way:
| Step Number | Description | Suggestions | Links |
|---|---|---|---|
| 1 | Download EV Charging APP | For Android For Apple | |
| 2 | Pair | Pairing code is the last six digits of your installer code which can be found on the sticker. | Pairing process |
| 3 | Update device to the latest FW | After pairing, choose your device in the menu, and a notification may suggest updating the firmware version. | How to update |
| 4 | Configure your TeltoCharge | Follow steps in device configuration guide and using Teltonika EV Charging app set parameters according to your site requirements. | Possible settings |
| 5 | Connect to Wifi | After ensuring the device is configured according to your site requirements, open "Connectivity" window in the app and connect device to the internet via Wi-Fi or LAN. | Connect to Wifi or LAN |
| 6 | Enable OCPP | Once the device is connected to the internet, go to the "OCPP" tab in "Connectivity" window and connect the charger to the Powerverse App by entering this URL: wss://ocpp.powerverse.com:443/ note: Make sure your phone doesn't auto correct wss. |
Connect to OCPP |
| Additional | LED indicators | Meaning of TeltoCharge LED indicators. | LED indicators |
Configuration Setup Possibilities
Home Installation Configuration with DLB and CT Clamps
| Step Number | Description | Suggestions | Links |
|---|---|---|---|
| 1 | Make sure CT clamps are mounted correctly. | You can check correct CT clamps installation option in this page above. | CT Scheme |
| 2 | Go to Installer Settings via EV Charging APP | Enter full 9-digit installer code to access installer menu. | Installer menu access |
| 3 | Go to Installation section | Set Max power from grid in amps according to your main circuit breaker value. | Installation section access |
| 4 | Go to Load Balancing section | 1. Select CT Clamp as measuring device. 2. Enable Load Balancing and press on DLB CT button. (Before calibration, ensure at least one CT is connected to the device and that its measuring end is not clamped around the cable) 3. Calibrate your CT clamp. |
How to calibrate CT clamp |
| 5 | Test setup | 1. Plug in cable from charger to EV, but don't start charging. 2. Go to Diagnostics window in the app and check if Max allowed current is more than at least 6 A to start charging. |
1. No limitations 2. Load balance limitations |