22 kW TeltoCharge Suggested configuration: Difference between revisions
Appearance
m Protected "22 kW TeltoCharge Suggested configuration" ([Edit=Allow only administrators] (indefinite) [Move=Allow only administrators] (indefinite)) |
No edit summary |
||
| (4 intermediate revisions by the same user not shown) | |||
| Line 3: | Line 3: | ||
Here you can find information about '''Suggested configuration of 22 kW power TeltoCharge installer menu''' parameters according to your '''electrical grid'''. | Here you can find information about '''Suggested configuration of 22 kW power TeltoCharge installer menu''' parameters according to your '''electrical grid'''. | ||
<br> | <br> | ||
<h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">1 phase (1L+N+PE) | voltage between L-N 230V ± 10%</h2> | |||
<ul style="list-style-type: none; margin: 0; padding: 0;"> | |||
<br> | |||
To run your 22 kW TeltoCharge on 1 phase, please follow this table below with suggested configurations. | |||
<h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">Suggested installer menu configuration guide</h2> | |||
<ul style="list-style-type: none; margin: 0; padding: 0;"> | |||
With 1-phase of 22 kW TeltoCharge you can achieve to charge at maximum 7.4 kW power. | |||
{| class="wikitable" style="text-align: center; border: 1px solid #0054A6; font-family: arial, sans-serif; width: 60%;" | |||
|- | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Option number in installer | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Installer menu parameter name | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 4px;" | Suggested value to set | |||
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Link to description of parameter | |||
|- | |||
| style="padding: 8px;" | 01 | |||
| style="padding: 8px;" | '''Max power from grid''' | |||
| style="padding: 8px;" | 32 A | |||
| style="padding: 8px;" | [[Max power from grid]] | |||
|- | |||
| style="padding: 8px;" | 02 | |||
| style="padding: 8px;" | '''Supply voltage ''' | |||
| style="padding: 20px;" | 230 V | |||
| style="padding: 8px;" | [[Supply voltage]] | |||
|- | |||
| style="padding: 8px;" | 03 | |||
| style="padding: 8px;" | '''Upper voltage tolerance''' | |||
| style="padding: 8px;" | 10 % | |||
| style="padding: 8px;" | [[Upper voltage tolerance]] | |||
|- | |||
| style="padding: 8px;" | 04 | |||
| style="padding: 8px;" | '''Lower voltage tolerance''' | |||
| style="padding: 8px;" | 10 % | |||
| style="padding: 8px;" | [[Lower voltage tolerance]] | |||
|- | |||
| style="padding: 8px;" | 05 | |||
| style="padding: 8px;" | '''Three phase charging''' | |||
| style="padding: 8px;" | OFF | |||
| style="padding: 8px;" | [[Three phase charging]] | |||
|- | |||
| style="padding: 8px;" | 06 | |||
| style="padding: 8px;" | '''Phase priority''' | |||
| style="padding: 8px;" | L1 | |||
| style="padding: 8px;" | [[Phase priority]] | |||
|- | |||
| style="padding: 8px;" | 07 | |||
| style="padding: 8px;" | '''Difference between phases''' | |||
| style="padding: 8px;" | 120 ° | |||
| style="padding: 8px;" | [[Difference between phases]] | |||
|- | |||
| style="padding: 8px;" | 08 | |||
| style="padding: 8px;" | '''Use neutral as phase''' | |||
| style="padding: 8px;" | OFF | |||
| style="padding: 8px;" | [[Use neutral as phase]] | |||
|- | |||
| style="padding: 8px;" | 09 | |||
| style="padding: 8px;" | '''Use data from energy meter''' | |||
| style="padding: 8px;" | OFF | |||
| style="padding: 8px;" | [[Use data from energy meter]] | |||
|- | |||
| style="padding: 8px;" | 10 | |||
| style="padding: 8px;" | '''kWh meter address''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.'' | |||
| style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters] | |||
|- | |||
| style="padding: 8px;" | 11 | |||
| style="padding: 8px;" | '''Energy meter type''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | |||
|- | |||
| style="padding: 8px;" | 12 | |||
| style="padding: 8px;" | '''RS-485 baudrate''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | |||
|- | |||
| style="padding: 8px;" | 13 | |||
| style="padding: 8px;" | '''RS-485 parity''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | |||
|- | |||
| style="padding: 8px;" | 14 | |||
| style="padding: 8px;" | '''RS-485 stop bit''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | |||
|- | |||
| style="padding: 8px;" | 15 | |||
| style="padding: 8px;" | '''Dynamic load balancing''' | |||
| style="padding: 8px;" | OFF | |||
| style="padding: 8px;" | [[Dynamic Load Balancing]] | |||
|- | |||
| style="padding: 8px;" | 16 | |||
| style="padding: 8px;" | '''Use preferred phase''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' | |||
| style="padding: 8px;" | [[Use prefered phase]] | |||
|- | |||
| style="padding: 8px;" | 17 | |||
| style="padding: 8px;" | '''Energy meter address''' | |||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | |||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters] | |||
|- | |||
| style="padding: 8px;" | 18 | |||
| style="padding: 8px;" | '''Allow simplified charging sequence''' | |||
| style="padding: 8px;" | OFF | |||
| style="padding: 8px;" | [[Allow simplified charging sequence]] | |||
|- | |||
| style="padding: 8px;" | 19 | |||
| style="padding: 8px;" | '''Charger location is ventilated''' | |||
| style="padding: 8px;" | OFF (if your TeltoCharge is inside the property) | |||
| style="padding: 8px;" | [[Charger location is ventilated]] | |||
|- | |||
| style="padding: 8px;" | 20 | |||
| style="padding: 8px;" | '''Temperature warning''' | |||
| style="padding: 8px;" | 60 °C | |||
| style="padding: 8px;" | [[Temperature warning]] | |||
|} | |||
<h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">3 phase (3L+N+PE) | voltage between L-N 230V ± 10% | L-L 400V ± 10%</h2> | <h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">3 phase (3L+N+PE) | voltage between L-N 230V ± 10% | L-L 400V ± 10%</h2> | ||
<ul style="list-style-type: none; margin: 0; padding: 0;"> | <ul style="list-style-type: none; margin: 0; padding: 0;"> | ||
| Line 38: | Line 150: | ||
| style="padding: 8px;" | 10 % | | style="padding: 8px;" | 10 % | ||
| style="padding: 8px;" | [[Lower voltage tolerance]] | | style="padding: 8px;" | [[Lower voltage tolerance]] | ||
|- | |- | ||
| style="padding: 8px;" | 05 | | style="padding: 8px;" | 05 | ||
| style="padding: 8px;" | '''Three phase charging''' | |||
| style="padding: 8px;" | ON | |||
| style="padding: 8px;" | [[Three phase charging]] | |||
|- | |||
| style="padding: 8px;" | 06 | |||
| style="padding: 8px;" | '''Phase priority''' | | style="padding: 8px;" | '''Phase priority''' | ||
| style="padding: 8px;" | L1 | | style="padding: 8px;" | L1 | ||
| style="padding: 8px;" | [[Phase priority]] | | style="padding: 8px;" | [[Phase priority]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 07 | ||
| style="padding: 8px;" | '''Difference between phases''' | | style="padding: 8px;" | '''Difference between phases''' | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 120 ° | ||
| style="padding: 8px;" | [[Difference between phases]] | | style="padding: 8px;" | [[Difference between phases]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 08 | ||
| style="padding: 8px;" | '''Use neutral as phase''' | | style="padding: 8px;" | '''Use neutral as phase''' | ||
| style="padding: 8px;" | OFF | | style="padding: 8px;" | OFF | ||
| style="padding: 8px;" | [[Use neutral as phase]] | | style="padding: 8px;" | [[Use neutral as phase]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 09 | ||
| style="padding: 8px;" | '''Use data from energy meter''' | | style="padding: 8px;" | '''Use data from energy meter''' | ||
| style="padding: 8px;" | OFF | | style="padding: 8px;" | OFF | ||
| style="padding: 8px;" | [[Use data from energy meter]] | | style="padding: 8px;" | [[Use data from energy meter]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 10 | ||
| style="padding: 8px;" | '''kWh meter address''' | | style="padding: 8px;" | '''kWh meter address''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.'' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.'' | ||
| style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters] | | style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 11 | ||
| style="padding: 8px;" | '''Energy meter type''' | | style="padding: 8px;" | '''Energy meter type''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | ||
|- | |- | ||
| style="padding: 8px;" | 12 | |||
| style="padding: 8px;" | | |||
| style="padding: 8px;" | '''RS-485 baudrate''' | | style="padding: 8px;" | '''RS-485 baudrate''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 13 | ||
| style="padding: 8px;" | '''RS-485 parity''' | | style="padding: 8px;" | '''RS-485 parity''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 14 | ||
| style="padding: 8px;" | '''RS-485 stop bit''' | | style="padding: 8px;" | '''RS-485 stop bit''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 15 | ||
| style="padding: 8px;" | '''Dynamic load balancing''' | | style="padding: 8px;" | '''Dynamic load balancing''' | ||
| style="padding: 8px;" | OFF | | style="padding: 8px;" | OFF | ||
| style="padding: 8px;" | [[Dynamic Load Balancing]] | | style="padding: 8px;" | [[Dynamic Load Balancing]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 16 | ||
| style="padding: 8px;" | '''Use preferred phase''' | | style="padding: 8px;" | '''Use preferred phase''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' | ||
| style="padding: 8px;" | [[Use prefered phase]] | | style="padding: 8px;" | [[Use prefered phase]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 17 | ||
| style="padding: 8px;" | '''Energy meter address''' | | style="padding: 8px;" | '''Energy meter address''' | ||
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | | style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.'' | ||
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters] | | style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 18 | ||
| style="padding: 8px;" | '''Allow simplified charging sequence''' | | style="padding: 8px;" | '''Allow simplified charging sequence''' | ||
| style="padding: 8px;" | OFF | | style="padding: 8px;" | OFF | ||
| style="padding: 8px;" | [[Allow simplified charging sequence]] | | style="padding: 8px;" | [[Allow simplified charging sequence]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 19 | ||
| style="padding: 8px;" | '''Charger location is ventilated''' | | style="padding: 8px;" | '''Charger location is ventilated''' | ||
| style="padding: 8px;" | OFF (if your TeltoCharge is inside the property) | | style="padding: 8px;" | OFF (if your TeltoCharge is inside the property) | ||
| style="padding: 8px;" | [[Charger location is ventilated]] | | style="padding: 8px;" | [[Charger location is ventilated]] | ||
|- | |- | ||
| style="padding: 8px;" | | | style="padding: 8px;" | 20 | ||
| style="padding: 8px;" | '''Temperature warning''' | | style="padding: 8px;" | '''Temperature warning''' | ||
| style="padding: 8px;" | 60 °C | | style="padding: 8px;" | 60 °C | ||
| style="padding: 8px;" | [[Temperature warning]] | | style="padding: 8px;" | [[Temperature warning]] | ||
|} | |} | ||
Latest revision as of 10:26, 18 July 2023
Introduction
-
Here you can find information about Suggested configuration of 22 kW power TeltoCharge installer menu parameters according to your electrical grid.
1 phase (1L+N+PE) | voltage between L-N 230V ± 10%
To run your 22 kW TeltoCharge on 1 phase, please follow this table below with suggested configurations.
-
With 1-phase of 22 kW TeltoCharge you can achieve to charge at maximum 7.4 kW power.
| Option number in installer | Installer menu parameter name | Suggested value to set | Link to description of parameter |
|---|---|---|---|
| 01 | Max power from grid | 32 A | Max power from grid |
| 02 | Supply voltage | 230 V | Supply voltage |
| 03 | Upper voltage tolerance | 10 % | Upper voltage tolerance |
| 04 | Lower voltage tolerance | 10 % | Lower voltage tolerance |
| 05 | Three phase charging | OFF | Three phase charging |
| 06 | Phase priority | L1 | Phase priority |
| 07 | Difference between phases | 120 ° | Difference between phases |
| 08 | Use neutral as phase | OFF | Use neutral as phase |
| 09 | Use data from energy meter | OFF | Use data from energy meter |
| 10 | kWh meter address | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - follow link on the right. |
Choose your Smart energy meter and its parameters |
| 11 | Energy meter type | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 12 | RS-485 baudrate | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 13 | RS-485 parity | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 14 | RS-485 stop bit | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 15 | Dynamic load balancing | OFF | Dynamic Load Balancing |
| 16 | Use preferred phase | Not needed to adjust if Dynamic load balancing is OFF. | Use prefered phase |
| 17 | Energy meter address | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. |
Choose your Smart energy meter and its parameters |
| 18 | Allow simplified charging sequence | OFF | Allow simplified charging sequence |
| 19 | Charger location is ventilated | OFF (if your TeltoCharge is inside the property) | Charger location is ventilated |
| 20 | Temperature warning | 60 °C | Temperature warning |
3 phase (3L+N+PE) | voltage between L-N 230V ± 10% | L-L 400V ± 10%
-
Follow these steps to get started with TeltoCharge in a maximum 22 kW power:
| Option number in installer | Installer menu parameter name | Suggested value to set | Link to description of parameter |
|---|---|---|---|
| 01 | Max power from grid | 32 A | Max power from grid |
| 02 | Supply voltage | 230 V | Supply voltage |
| 03 | Upper voltage tolerance | 10 % | Upper voltage tolerance |
| 04 | Lower voltage tolerance | 10 % | Lower voltage tolerance |
| 05 | Three phase charging | ON | Three phase charging |
| 06 | Phase priority | L1 | Phase priority |
| 07 | Difference between phases | 120 ° | Difference between phases |
| 08 | Use neutral as phase | OFF | Use neutral as phase |
| 09 | Use data from energy meter | OFF | Use data from energy meter |
| 10 | kWh meter address | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - follow link on the right. |
Choose your Smart energy meter and its parameters |
| 11 | Energy meter type | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 12 | RS-485 baudrate | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 13 | RS-485 parity | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 14 | RS-485 stop bit | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. | |
| 15 | Dynamic load balancing | OFF | Dynamic Load Balancing |
| 16 | Use preferred phase | Not needed to adjust if Dynamic load balancing is OFF. | Use prefered phase |
| 17 | Energy meter address | Not needed to adjust if Dynamic load balancing is OFF. If it's ON - you must follow link on the right. |
Choose your Smart energy meter and its parameters |
| 18 | Allow simplified charging sequence | OFF | Allow simplified charging sequence |
| 19 | Charger location is ventilated | OFF (if your TeltoCharge is inside the property) | Charger location is ventilated |
| 20 | Temperature warning | 60 °C | Temperature warning |