= Modbus RTU meters = | = Modbus RTU meters = | ||
== Eastron SDM 230-M (1PH) and SDM 72D-M (3PH) == | == Eastron SDM 230-M (1PH) and SDM 72D-M (3PH) == | ||
=== Description === | |||
Modbus RTU meters are a stable and efficient solution, especially when the electrical cabinet already requires to be cleaned up and adapted for an EV charger installation. Since the connection is wired it ensures a great latency and can be of help in especially low power or high-power installations, where even small delays are relevant to be addressed immediately. Robust and industrial solution for long time usage. Good for places with unstable Wi-Fi connectivity. 1 phase and 3 phase versions available. | |||
=== Datasheets === | === Datasheets === | ||
[[ | [[Media:SDM230 series Datasheet.pdf|SDM230 series Datasheet]] | ||
[[Media:EASTRON SDM72D-M DATASHEET.pdf|EASTRON SDM72D-M datasheet]] | |||
=== Manual === | === Manual === | ||
[[ | |||
[[Media:SDM230-M MID datasheet.pdf|SDM230-M MID manual]] | |||
[[Media:SDM72D-M user manual.pdf|SDM72D-M user manual]] | [[Media:SDM72D-M user manual.pdf|SDM72D-M user manual]] | ||
=== Certification and declarations === | === Certification and declarations === | ||
[[ | [[Media:Eastron SDM230 Declaration.pdf|Eastron SDM230 MID]] | ||
[[ | [[Media:Eastron SDM72 MID.pdf|Eastron SDM72 MID]] | ||
=== Wiring scheme === | |||
[https://wiki.teltonika-energy.com/images/5/53/Eastron_sdm72.png SDM 72D-M Wiring scheme] | |||
=== Set up === | |||
[[Eastron_settings|Settings]] | |||
[[Dynamic_Load_Balancing_EVC2#SMART_METER_AND_TELTOCHARGE_COMMUNICATION|Set up]] | |||
=== Technical data === | === Technical data === | ||
{| class="wikitable" | |||
|Model | |||
| colspan="3" | SDM72D/BR/BI | |||
|- | |||
|Nominal voltage(Un) | |||
| colspan="3" | 3x230/400 V ac | |||
|- | |||
|Operational voltage | |||
| colspan="3" | 80%~120% of Un | |||
|- | |||
|Insulation capabilities - AC voltage withstand | |||
| colspan="3" | 4kV for 1 minute | |||
|- | |||
|Insulation capabilities - Impulse voltage withstand | |||
| colspan="3" | 6kV-1.2µS | |||
|- | |||
|Basic current (Ib) | |||
| colspan="3" | 10A | |||
|- | |||
|Maximum rated current (Imax) | |||
| colspan="3" | 100A | |||
|- | |||
|Operational current range | |||
| colspan="3" | 0.4% Ib–Imax | |||
|- | |||
|Over current withstand | |||
| colspan="3" | 30 Imax for 0.01s | |||
|- | |||
|Operational frequency range | |||
| colspan="3" | 50 or 60Hz | |||
|- | |||
|Power consumption per phase | |||
| colspan="3" | ≤2W/10VA | |||
|- | |||
|Pulse output | |||
| colspan="3" | 1000imp/kWh | |||
|- | |||
|Display | |||
| colspan="3" | LCD | |||
|- | |||
|Max reading | |||
| colspan="3" | 999999.9 kWh | |||
|- | |||
! colspan="4" | Performance criteria | |||
|- | |||
|Operating humidity | |||
| colspan="3" | ≤90% | |||
|- | |||
|Storage humidity | |||
| colspan="3" | ≤95% | |||
|- | |||
|Operating temperature | |||
| colspan="3" | -25°C ~ +55°C | |||
|- | |||
|Storage temperature | |||
| colspan="3" | -40°C ~ +70°C | |||
|- | |||
|Reference temperature | |||
| colspan="3" | 23°C ± 2°C | |||
|- | |||
|International standard | |||
| colspan="3" | IEC 62053-21 / EN50470-1/3 | |||
|- | |||
! colspan="4" | Additional characteristics | |||
|- | |||
|Accuracy class | |||
| colspan="3" | Class1/Class B | |||
|- | |||
|Installation category | |||
| colspan="3" | CAT III | |||
|- | |||
|Mechanical environment | |||
| colspan="3" | M1 | |||
|- | |||
|Electromagnetic environment | |||
| colspan="3" | E2 | |||
|- | |||
|Degree of pollution | |||
| colspan="3" | 2 | |||
|- | |||
|Protection against penetration of dust and water | |||
| colspan="3" | IP51 (indoor) | |||
|- | |||
|Insulating encased meter or protective class | |||
| colspan="3" | II | |||
|- | |||
|Altitude | |||
| colspan="3" | up to 2000m | |||
|- | |||
|Electrostatic discharges | |||
| colspan="3" | 8kV contact / 15kV air gap | |||
|- | |||
|Electromagnetic HF fields | |||
| colspan="3" | IEC 61000-4-3 | |||
|- | |||
|Electrical fast transients | |||
| colspan="3" | 4kV | |||
|- | |||
|Surge | |||
| colspan="3" | 4kV | |||
|- | |||
|Radiated & conducted emissions | |||
| colspan="3" | EN 55022 | |||
|- | |||
! colspan="4" | Modbus | |||
|- | |||
|Bus type | |||
| colspan="3" | RS485 (semi-duplex) | |||
|- | |||
|Protocol | |||
| colspan="3" | Modbus RTU | |||
|- | |||
|Baud rate | |||
| colspan="3" | 1200/2400/4800/9600bps | |||
|- | |||
|Address range | |||
| colspan="3" | 1–247 | |||
|- | |||
|Max. bus loading | |||
| colspan="3" | 64 pcs | |||
|- | |||
|Communication distance | |||
| colspan="3" | 1000M | |||
|- | |||
|Parity | |||
| colspan="3" | EVEN/ODD/NONE | |||
|- | |||
|Data bit | |||
| colspan="3" | 8 | |||
|- | |||
|Stop bit | |||
| colspan="3" | 1 | |||
|} | |||