Modbus TCP meters: Difference between revisions
No edit summary |
m FiodorF moved page EVC2 Modbus TCP meters to Modbus TCP meters |
||
| (16 intermediate revisions by 2 users not shown) | |||
| Line 1: | Line 1: | ||
= Modbus TCP meters = | = Modbus TCP meters = | ||
Modbus TCP meters allow for more flexibility in the installation. Since they use local network connectivity usually both wired and wireless options are available depending on the installation needs. The installation is also faster, since the meters need less space and work with the electrical cabinet, as the measurements are done via CT clamps that connect to the meter. It also allows for load balance in situations, where power cables have been prepared in advance, without preparing any data cables, or if the distances from electrical cabinet to the charger location are very long. | |||
= | == Shelly PRO-3EM == | ||
=== Description === | |||
Shelly Pro 3EM is a DIN-rail-mounted, three-phase energy meter that can operate locally over LAN or Wi-Fi, or connect to cloud and home automation systems. The device can be remotely accessed, configured, and monitored through the same network infrastructure, and its built-in web interface allows users to monitor and adjust settings. | |||
=== Wiring diagram === | |||
[[File:Pro-3EM-wiring-diagram-with-fuses.png|alt=Pro-3EM-wiring-diagram|frameless]] | |||
=== User and safety guide === | |||
[[Media:Shelly Pro 3EM multilingual printed user and safety guide.pdf|Shelly Pro 3EM user and safety guide]] | |||
=== Resources === | |||
[https://www.shelly.com/blogs/documentation/shelly-pro-3em?srsltid=AfmBOopPoEcc-LmzmIZMtuASYl7jvN4q449i6NRq6XhfFm3q_Oo8MCUt Manufacturers documentation page] | |||
=== Certificates and conformity declarations === | |||
[[Media:Shelly Pro 3EM multilingual EU declaration of conformity 2025-07-23.pdf|EU]] | |||
[[Media:Shelly Pro 3EM 120A UK PSTI ACT Statement of compliance.pdf|UK]] | |||
[[Media:Shelly Pro 3EM AU NZ Certificate for Suitability.pdf|AU and NZ]] | |||
=== Technical data === | |||
{| class="wikitable" | |||
! colspan="1" rowspan="1" |Type | |||
! colspan="1" rowspan="1" |Value | |||
|- | |||
| colspan="2" rowspan="1" |'''Physical''' | |||
|- | |||
| colspan="1" rowspan="1" |Size (HxWxD): | |||
| colspan="1" rowspan="1" |94x19x69 ±0.5 mm / 3.70x0.75x2.71 ±0.02 in | |||
|- | |||
| colspan="1" rowspan="1" |Weight: | |||
| colspan="1" rowspan="1" |62 ±1 g / 2.19 ±0.05 oz | |||
|- | |||
| colspan="1" rowspan="1" |Mounting: | |||
| colspan="1" rowspan="1" |DIN rail | |||
|- | |||
| colspan="1" rowspan="1" |Screw terminals max torque: | |||
| colspan="1" rowspan="1" |0.4 Nm / 4.43 lbin | |||
|- | |||
| colspan="1" rowspan="1" |Conductor cross section: | |||
| colspan="1" rowspan="1" |0.5 to 2.5 mm² / 20 to 14 AWG (solid, stranded, and bootlace lugs) | |||
|- | |||
| colspan="1" rowspan="1" |Conductor stripped length: | |||
| colspan="1" rowspan="1" |6 to 7 mm / 0.24 to 0.28 in | |||
|- | |||
| colspan="1" rowspan="1" |Shell material: | |||
| colspan="1" rowspan="1" |Plastic | |||
|- | |||
| colspan="1" rowspan="1" |Color: | |||
| colspan="1" rowspan="1" |White | |||
|- | |||
| colspan="2" rowspan="1" |'''Environmental''' | |||
|- | |||
| colspan="1" rowspan="1" |Ambient temperature: | |||
| colspan="1" rowspan="1" |-20 °C to 40 °C / -5 °F to 105 °F | |||
|- | |||
| colspan="1" rowspan="1" |Humidity: | |||
| colspan="1" rowspan="1" |30 % to 70 % RH | |||
|- | |||
| colspan="1" rowspan="1" |Max. altitude: | |||
| colspan="1" rowspan="1" |2000 m / 6562 ft | |||
|- | |||
| colspan="2" rowspan="1" |'''Electrical''' | |||
|- | |||
| colspan="1" rowspan="1" |Power supply voltage AC: | |||
| colspan="1" rowspan="1" |100 - 260 V, 50/60 Hz | |||
|- | |||
| colspan="1" rowspan="1" |Power supply voltage DC: | |||
| colspan="1" rowspan="1" |N/A | |||
|- | |||
| colspan="1" rowspan="1" |Power consumption: | |||
| colspan="1" rowspan="1" |< 3 W | |||
|- | |||
| colspan="1" rowspan="1" |External protection: | |||
| colspan="1" rowspan="1" |Tripping characteristic B or C, | |||
16A max. rated current, | |||
min. 6 kA interrupting rating, | |||
energy limiting class 3 | |||
|- | |||
| colspan="2" rowspan="1" |'''Sensors, meters''' | |||
|- | |||
| colspan="1" rowspan="1" |Internal-temperature sensor: | |||
| colspan="1" rowspan="1" |Yes | |||
|- | |||
| colspan="1" rowspan="1" |Voltmeters (RMS for each phase): | |||
| colspan="1" rowspan="1" |100 - 260 V | |||
|- | |||
| colspan="1" rowspan="1" |Voltmeters accuracy: | |||
| colspan="1" rowspan="1" |±1 % | |||
|- | |||
| colspan="1" rowspan="1" |Ammeters (RMS via CT for each phase and the Neutral): | |||
| colspan="1" rowspan="1" |0 - 120 A | |||
|- | |||
| colspan="1" rowspan="1" |Compatible CT | |||
| colspan="1" rowspan="1" |CT 120A | |||
|- | |||
| colspan="1" rowspan="1" |Ammeters accuracy: | |||
| colspan="1" rowspan="1" |±1 % (2 - 120 A), ±2 % (1 - 2 A), ±5 % (0 - 1 A) | |||
|- | |||
| colspan="1" rowspan="1" |Power and energy meters: | |||
| colspan="1" rowspan="1" | | |||
* Active and apparent power | |||
* Active and apparent energy | |||
* Power factor | |||
* Fundamental active and fundamental reactive energy | |||
|- | |||
| colspan="1" rowspan="1" |Channel-to-channel calibration minimum load | |||
| colspan="1" rowspan="1" |500 W per channel | |||
|- | |||
| colspan="1" rowspan="1" |No load threshold: | |||
| colspan="1" rowspan="1" |30 VA per channel | |||
|- | |||
| colspan="1" rowspan="1" |Measurement data storage: | |||
| colspan="1" rowspan="1" |At least 60 days of 1 min data resolution | |||
|- | |||
| colspan="1" rowspan="1" |Data export: | |||
| colspan="1" rowspan="1" | | |||
* CSV for PQ recorded values | |||
* JSON format export through RPC | |||
|- | |||
| colspan="2" rowspan="1" |'''Radio''' | |||
|- | |||
| colspan="1" rowspan="1" |RF band: | |||
| colspan="1" rowspan="1" |2400 - 2495 MHz | |||
|- | |||
| colspan="1" rowspan="1" |Max. RF power: | |||
| colspan="1" rowspan="1" |<20 dBm | |||
|- | |||
| colspan="1" rowspan="1" |Wi-Fi protocol: | |||
| colspan="1" rowspan="1" |802.11 b/g/n | |||
|- | |||
| colspan="1" rowspan="1" |Wi-Fi Range: | |||
| colspan="1" rowspan="1" |Up to 30 m / 100 ft indoors and 50 m / 160 ft outdoors | |||
(Depends on local conditions) | |||
|- | |||
| colspan="1" rowspan="1" |Bluetooth Protocol: | |||
| colspan="1" rowspan="1" |4.2 | |||
|- | |||
| colspan="1" rowspan="1" |Bluetooth Range: | |||
| colspan="1" rowspan="1" |Up to 10 m / 33 ft indoors and 30 m / 100 ft outdoors | |||
(Depends on local conditions) | |||
|- | |||
| colspan="2" rowspan="1" |'''MCU''' | |||
|- | |||
| colspan="1" rowspan="1" |CPU: | |||
| colspan="1" rowspan="1" |ESP32-D0WDQ6 | |||
|- | |||
| colspan="1" rowspan="1" |Flash: | |||
| colspan="1" rowspan="1" |16 MB | |||
|- | |||
| colspan="2" rowspan="1" |'''Firmware capabilities''' | |||
|- | |||
| colspan="1" rowspan="1" |Webhooks (URL actions): | |||
| colspan="1" rowspan="1" |20 with 5 URLs per hook | |||
|- | |||
| colspan="1" rowspan="1" |Scripting: | |||
| colspan="1" rowspan="1" |Yes | |||
|- | |||
| colspan="1" rowspan="1" |MQTT: | |||
| colspan="1" rowspan="1" |Yes | |||
|- | |||
| colspan="1" rowspan="1" |CoAP: | |||
| colspan="1" rowspan="1" |No | |||
|} | |||
== EASTRON SEM 3 WL == | |||
=== Description === | |||
Eastron SEM3 is a new generation din rail mounted energy meter, equipped with Wi-Fi and RS485 connectivity. The meter can be used as 1x 3phase energy meter or 3 individual single phase energy meter. In single phase mode, 3 external CTs can be set with different CT ratio for three independent loads. | |||
=== Wiring diagram === | |||
[[File:Eastron wiring.png|alt=Eastron SEM 3WL wiring diagram|frameless]] | |||
===Wi-Fi Configuration=== | |||
You may find the installation instructions on page 11 of the [[:File:Eastron SEM 3 WL manual.pdf|official manual]]. | |||
=== Electrical, Mechanical, Environmental, EMC and Safety Characteristics === | |||
{| class="wikitable" | |||
! colspan="3" | Electrical Characteristics | |||
|- | |||
! Type of Measurement | |||
| colspan="2" | RMS, Including Harmonics, on Three Phase AC System (3P+N) | |||
|- | |||
! rowspan="7" | Measurement Accuracy | |||
! Power | |||
| ± 1% IEC 61557-12 Class 1 | |||
|- | |||
! Active Energy | |||
| ± 1% | |||
|- | |||
! Reactive Energy | |||
| ± 2% | |||
|- | |||
! Frequency | |||
| ± 0.2% | |||
|- | |||
! Current | |||
| ± 0.5% (4A to 120A)<br>± 1% (1A to 4A)<br>± 3% (0.06A to 1A) | |||
|- | |||
! Voltage | |||
| ± 0.5% | |||
|- | |||
! Power Factor | |||
| ± 0.1 | |||
|- | |||
! Data Update Rate | |||
| colspan="2" | Active Power: 50ms (RS485), 100ms (Wi-Fi) | |||
|- | |||
! rowspan="3" | Input-Voltage | |||
! U<sub>n</sub> | |||
| 3*230V L-N / 3*400V L-L | |||
|- | |||
! Working Voltage Range | |||
| 90 to 277 V ac L-N<br>156 to 480 V ac L-L | |||
|- | |||
! Frequency Range | |||
| 50/60Hz | |||
|- | |||
! colspan="3" | Mechanical Characteristics | |||
|- | |||
! Weight | |||
| colspan="2" | ≈100g (SEM3) | |||
|- | |||
! IP Degree of Protection<br>(IEC 60529) | |||
| colspan="2" | IP51 Front Display<br>IP20 Whole Meter | |||
|- | |||
! Dimensions (DxHxW) | |||
| colspan="2" | 68.5*90*19mm | |||
|- | |||
! Mounting | |||
| colspan="2" | DIN Rail 35mm | |||
|- | |||
! Material of Meter Case | |||
| colspan="2" | Self-extinguishing UL 94 V-0 | |||
|- | |||
! Mechanical Environment | |||
| colspan="2" | M1 | |||
|- | |||
! colspan="3" | Environmental Characteristics | |||
|- | |||
! Operating Temperature | |||
| colspan="2" | -40°C to +70°C | |||
|- | |||
! Storage Temperature | |||
| colspan="2" | -40°C to +85°C | |||
|- | |||
! Humidity Rating | |||
| colspan="2" | ≤95% RH, non-condensing | |||
|- | |||
! Pollution Degree | |||
| colspan="2" | 2 | |||
|- | |||
! Altitude | |||
| colspan="2" | Up to 2000m | |||
|- | |||
! Vibration | |||
| colspan="2" | 10Hz to 50Hz, IEC 60068-2-6 | |||
|- | |||
! colspan="3" | Electromagnetic Compatibility | |||
|- | |||
! Electrostatic Discharge | |||
| colspan="2" | IEC 61000-4-2 | |||
|- | |||
! Immunity to Radiated Fields | |||
| colspan="2" | IEC 61000-4-3 | |||
|- | |||
! Immunity to Fast Transients | |||
| colspan="2" | IEC 61000-4-4 | |||
|- | |||
! Immunity to Impulse Waves | |||
| colspan="2" | IEC 61000-4-5 | |||
|- | |||
! Conducted Immunity | |||
| colspan="2" | IEC 61000-4-6 | |||
|- | |||
! Immunity to Magnetic Fields | |||
| colspan="2" | IEC 61000-4-8 | |||
|- | |||
! Immunity to Voltage Dips | |||
| colspan="2" | IEC 61000-4-11 | |||
|- | |||
! Radiated Emissions | |||
| colspan="2" | EN55032 Class B | |||
|- | |||
! Conducted Emissions | |||
| colspan="2" | EN55032 Class B | |||
|- | |||
! colspan="3" | Safety | |||
|- | |||
! Measurement Category | |||
| colspan="2" | Per IEC61010-1 CAT III | |||
|- | |||
! Current Inputs | |||
| colspan="2" | Require External Current Transformer for Isolation | |||
|- | |||
!Over-voltage Category | |||
| colspan="2" | CAT III | |||
|- | |||
!Protective Class | |||
| colspan="2" | II | |||
|- | |||
! colspan="3" | Communications | |||
|- | |||
! Interface 1 | |||
! colspan="2" | RS485 Port | |||
|- | |||
! Interface 1 Protocol | |||
| colspan="2"| MODBUS RTU | |||
|- | |||
! Communication Address | |||
| colspan="2"| 1 to 247 | |||
|- | |||
! Transmission Mode | |||
| colspan="2"| Half Duplex | |||
|- | |||
! Data Type | |||
| colspan="2"| Floating Point | |||
|- | |||
! Transmission Distance | |||
| colspan="2"| 1000m Maximum | |||
|- | |||
! Transmission Speed | |||
| colspan="2"| 2400/4800/9600/19200/38400/115200bps | |||
|- | |||
! Parity | |||
| colspan="2"| NONE (Default) / ODD / EVEN | |||
|- | |||
! Stop Bits | |||
| colspan="2"| 1 or 2 | |||
|- | |||
! Response Time | |||
| colspan="2"| <50 ms | |||
|- | |||
! Interface 2 | |||
! colspan="2" | Wi-Fi | |||
|- | |||
! Interface 2 Protocol | |||
| colspan="2"| MODBUS TCP | |||
|- | |||
! Data Type | |||
| colspan="2"| Floating Point | |||
|- | |||
! RF Band | |||
| colspan="2"| 2.4 GHz to 2.5 GHz | |||
|- | |||
! Max. RF Power | |||
| colspan="2"| <20 dBm | |||
|- | |||
! Wi-Fi Protocol | |||
| colspan="2"| 802.11 b/g/n | |||
|- | |||
! Wi-Fi Range | |||
| colspan="2"| Up to 30m / 100ft indoors and 50m / 160ft outdoors<br>(Depends on local conditions) | |||
|} | |||
__FORCETOC__ | __FORCETOC__ | ||
Latest revision as of 11:05, 14 October 2026
Modbus TCP meters
Modbus TCP meters allow for more flexibility in the installation. Since they use local network connectivity usually both wired and wireless options are available depending on the installation needs. The installation is also faster, since the meters need less space and work with the electrical cabinet, as the measurements are done via CT clamps that connect to the meter. It also allows for load balance in situations, where power cables have been prepared in advance, without preparing any data cables, or if the distances from electrical cabinet to the charger location are very long.
Shelly PRO-3EM
Description
Shelly Pro 3EM is a DIN-rail-mounted, three-phase energy meter that can operate locally over LAN or Wi-Fi, or connect to cloud and home automation systems. The device can be remotely accessed, configured, and monitored through the same network infrastructure, and its built-in web interface allows users to monitor and adjust settings.
Wiring diagram
User and safety guide
Shelly Pro 3EM user and safety guide
Resources
Manufacturers documentation page
Certificates and conformity declarations
Technical data
| Type | Value |
|---|---|
| Physical | |
| Size (HxWxD): | 94x19x69 ±0.5 mm / 3.70x0.75x2.71 ±0.02 in |
| Weight: | 62 ±1 g / 2.19 ±0.05 oz |
| Mounting: | DIN rail |
| Screw terminals max torque: | 0.4 Nm / 4.43 lbin |
| Conductor cross section: | 0.5 to 2.5 mm² / 20 to 14 AWG (solid, stranded, and bootlace lugs) |
| Conductor stripped length: | 6 to 7 mm / 0.24 to 0.28 in |
| Shell material: | Plastic |
| Color: | White |
| Environmental | |
| Ambient temperature: | -20 °C to 40 °C / -5 °F to 105 °F |
| Humidity: | 30 % to 70 % RH |
| Max. altitude: | 2000 m / 6562 ft |
| Electrical | |
| Power supply voltage AC: | 100 - 260 V, 50/60 Hz |
| Power supply voltage DC: | N/A |
| Power consumption: | < 3 W |
| External protection: | Tripping characteristic B or C,
16A max. rated current, min. 6 kA interrupting rating, energy limiting class 3 |
| Sensors, meters | |
| Internal-temperature sensor: | Yes |
| Voltmeters (RMS for each phase): | 100 - 260 V |
| Voltmeters accuracy: | ±1 % |
| Ammeters (RMS via CT for each phase and the Neutral): | 0 - 120 A |
| Compatible CT | CT 120A |
| Ammeters accuracy: | ±1 % (2 - 120 A), ±2 % (1 - 2 A), ±5 % (0 - 1 A) |
| Power and energy meters: |
|
| Channel-to-channel calibration minimum load | 500 W per channel |
| No load threshold: | 30 VA per channel |
| Measurement data storage: | At least 60 days of 1 min data resolution |
| Data export: |
|
| Radio | |
| RF band: | 2400 - 2495 MHz |
| Max. RF power: | <20 dBm |
| Wi-Fi protocol: | 802.11 b/g/n |
| Wi-Fi Range: | Up to 30 m / 100 ft indoors and 50 m / 160 ft outdoors
(Depends on local conditions) |
| Bluetooth Protocol: | 4.2 |
| Bluetooth Range: | Up to 10 m / 33 ft indoors and 30 m / 100 ft outdoors
(Depends on local conditions) |
| MCU | |
| CPU: | ESP32-D0WDQ6 |
| Flash: | 16 MB |
| Firmware capabilities | |
| Webhooks (URL actions): | 20 with 5 URLs per hook |
| Scripting: | Yes |
| MQTT: | Yes |
| CoAP: | No |
EASTRON SEM 3 WL
Description
Eastron SEM3 is a new generation din rail mounted energy meter, equipped with Wi-Fi and RS485 connectivity. The meter can be used as 1x 3phase energy meter or 3 individual single phase energy meter. In single phase mode, 3 external CTs can be set with different CT ratio for three independent loads.
Wiring diagram
Wi-Fi Configuration
You may find the installation instructions on page 11 of the official manual.
Electrical, Mechanical, Environmental, EMC and Safety Characteristics
| Electrical Characteristics | ||
|---|---|---|
| Type of Measurement | RMS, Including Harmonics, on Three Phase AC System (3P+N) | |
| Measurement Accuracy | Power | ± 1% IEC 61557-12 Class 1 |
| Active Energy | ± 1% | |
| Reactive Energy | ± 2% | |
| Frequency | ± 0.2% | |
| Current | ± 0.5% (4A to 120A) ± 1% (1A to 4A) ± 3% (0.06A to 1A) | |
| Voltage | ± 0.5% | |
| Power Factor | ± 0.1 | |
| Data Update Rate | Active Power: 50ms (RS485), 100ms (Wi-Fi) | |
| Input-Voltage | Un | 3*230V L-N / 3*400V L-L |
| Working Voltage Range | 90 to 277 V ac L-N 156 to 480 V ac L-L | |
| Frequency Range | 50/60Hz | |
| Mechanical Characteristics | ||
| Weight | ≈100g (SEM3) | |
| IP Degree of Protection (IEC 60529) |
IP51 Front Display IP20 Whole Meter | |
| Dimensions (DxHxW) | 68.5*90*19mm | |
| Mounting | DIN Rail 35mm | |
| Material of Meter Case | Self-extinguishing UL 94 V-0 | |
| Mechanical Environment | M1 | |
| Environmental Characteristics | ||
| Operating Temperature | -40°C to +70°C | |
| Storage Temperature | -40°C to +85°C | |
| Humidity Rating | ≤95% RH, non-condensing | |
| Pollution Degree | 2 | |
| Altitude | Up to 2000m | |
| Vibration | 10Hz to 50Hz, IEC 60068-2-6 | |
| Electromagnetic Compatibility | ||
| Electrostatic Discharge | IEC 61000-4-2 | |
| Immunity to Radiated Fields | IEC 61000-4-3 | |
| Immunity to Fast Transients | IEC 61000-4-4 | |
| Immunity to Impulse Waves | IEC 61000-4-5 | |
| Conducted Immunity | IEC 61000-4-6 | |
| Immunity to Magnetic Fields | IEC 61000-4-8 | |
| Immunity to Voltage Dips | IEC 61000-4-11 | |
| Radiated Emissions | EN55032 Class B | |
| Conducted Emissions | EN55032 Class B | |
| Safety | ||
| Measurement Category | Per IEC61010-1 CAT III | |
| Current Inputs | Require External Current Transformer for Isolation | |
| Over-voltage Category | CAT III | |
| Protective Class | II | |
| Communications | ||
| Interface 1 | RS485 Port | |
| Interface 1 Protocol | MODBUS RTU | |
| Communication Address | 1 to 247 | |
| Transmission Mode | Half Duplex | |
| Data Type | Floating Point | |
| Transmission Distance | 1000m Maximum | |
| Transmission Speed | 2400/4800/9600/19200/38400/115200bps | |
| Parity | NONE (Default) / ODD / EVEN | |
| Stop Bits | 1 or 2 | |
| Response Time | <50 ms | |
| Interface 2 | Wi-Fi | |
| Interface 2 Protocol | MODBUS TCP | |
| Data Type | Floating Point | |
| RF Band | 2.4 GHz to 2.5 GHz | |
| Max. RF Power | <20 dBm | |
| Wi-Fi Protocol | 802.11 b/g/n | |
| Wi-Fi Range | Up to 30m / 100ft indoors and 50m / 160ft outdoors (Depends on local conditions) | |