RCD - residual current device: Difference between revisions
Created page with "== Disclaimer == === RCD - residual current device === Charger shall be installed on power line with RCD Type B. If house grid already has it pre-installed, then additional i..." |
No edit summary |
||
| (4 intermediate revisions by 2 users not shown) | |||
| Line 2: | Line 2: | ||
=== RCD - residual current device === | === RCD - residual current device === | ||
In order to successfully use Teltocharge product, | In order to successfully use Teltocharge product, user's electrical grid must include a dedicated RCD Type B. RCD must be installed by experienced electrician, who installs it in parallel with the charger. Residual current device is not included with the package and has to be bought separately. | ||
If the house grid already has it pre-installed, then additional ones are not required. <br> | |||
Legitimate options: | |||
'''Installation option 1:''' | '''Installation option 1:''' | ||
Residual current protection (RCBO) type B with tripping current 30 mA and with | Residual current protection (RCBO) type B with tripping current 30 mA and with at least 32 A overcurrent protection (it is recommended to use 40 A) according to at least one of the standards IEC 61009-1 or IEC 60947-2. | ||
'''Installation option 2:''' | '''Installation option 2:''' | ||
Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61009-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection (MCB) rated for | Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61009-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection (MCB) rated for at least 32 A (it is recommended to use 40 A) should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series. | ||
'''Installation option 3:''' <br> | '''Installation option 3:''' <br> | ||
RCD Type A and appropriate equipment that ensures the disconnection of the supply in case of DC fault current above 6 mA. DC disconnection equipment must meet IEC 62955 standard requirements. | RCD Type A and appropriate equipment that ensures the disconnection of the supply in case of DC fault current above 6 mA. DC disconnection equipment must meet IEC 62955 standard requirements. | ||
<br> | <br> | ||
Before buying, please consult with the company | Before buying, please consult with the company that installs the product. | ||
[[Category: Getting Started]] | |||
Latest revision as of 14:22, 10 August 2026
Main Page > TeltoCharge > Getting Started > RCD - residual current deviceDisclaimer
RCD - residual current device
In order to successfully use Teltocharge product, user's electrical grid must include a dedicated RCD Type B. RCD must be installed by experienced electrician, who installs it in parallel with the charger. Residual current device is not included with the package and has to be bought separately.
If the house grid already has it pre-installed, then additional ones are not required.
Legitimate options:
Installation option 1:
Residual current protection (RCBO) type B with tripping current 30 mA and with at least 32 A overcurrent protection (it is recommended to use 40 A) according to at least one of the standards IEC 61009-1 or IEC 60947-2.
Installation option 2:
Residual current protection (RCCB or RCD) type B with tripping current 30 mA according to at least one of the standards IEC 61008-1 or IEC 61009-1 or IEC 60947-2 or IEC 62423. Additionally overcurrent protection (MCB) rated for at least 32 A (it is recommended to use 40 A) should be installed and have to be in accordance to at least one of the following standards: IEC 60947-2, IEC 60947-6-2, IEC 61009-1, IEC 60898 series or IEC 60269 series.
Installation option 3:
RCD Type A and appropriate equipment that ensures the disconnection of the supply in case of DC fault current above 6 mA. DC disconnection equipment must meet IEC 62955 standard requirements.
Before buying, please consult with the company that installs the product.