An RCBO (Residual Current Circuit Breaker with Overcurrent protection) is a single electrical safety device that combines the functions of a Residual Current Device (RCD) and a Miniature Circuit Breaker (MCB). It protects circuits from two types of electrical faults: earth leakage currents (which RCDs protect against) and overcurrents (like overloads and short circuits, which MCBs protect against). If the household already does not posses a seperate RCD, this device allows to speed up the charger installation with a combined device  to safely operate the EV charger. 1 phase and 3 phase versions available.
= Datasheet =
= Datasheet =


[[File:EKL5-63(H) RCBO 2 1.pdf|thumb|left|alt=RCBO datasheet|RCBO datasheet 3PH/1PH]]


[[Media:EKL5-63(H) RCBO 2 1.pdf|EKL-63 RCBO]]
[[Media:EKL5-63(H) RCBO 2 1.pdf|EKL-63 RCBO]]


= Certificates =
[[Media:Certificate of EKL5-63 CE and CB.pdf|CE and CB]]


= Technical data =
{| class="wikitable"
|Standard
| colspan="3" |IEC/EN61009-1
|-
|Protection
| colspan="3" |Ground fault, Overcurrent and short circuit
|-
| colspan="1" rowspan="2" |Type of trip
| colspan="3" |Ground fault: Electronic
|-
| colspan="3" |Overload and short circuit: Thermo-magnetic
|-
|Type of protection (electric leakage)
| colspan="3" |AC, A, S
|-
|No. of poles
| colspan="3" |1P+N 3module, 3P+N 5 module, N line with disconnected
|-
|Rated current In
| colspan="3" |6,10,16,20,25,32,40,50,63A
|-
|Rated voltage Ue
| colspan="3" |1P+N:230/240V~, 3P+N:400/415V~
|-
|Rated frequency
| colspan="3" |50/60Hz
|-
|Rated sensitivity currents I△n
| colspan="3" |10,30,100,300mA
|-
|Residual current off-time under I△n
| colspan="3" |≤0.1s
|-
|Rated residual making and breaking capacity(I△m)
| colspan="3" |500A(In≤50A),10In (In>50A)
|-
|Rated breaking capacity
| colspan="3" |EKL5-63: 6,000A, EKL5-63H: 10,000A
|-
|Energy limiting class
| colspan="3" |3
|-
|Rated impulse withstand voltage (1.2/50) Uimp
| colspan="3" |4,000V
|-
|Dielectric test voltage at ind. Freq. for 1min
| colspan="3" |2kV
|-
|Thermal release characteristic
| colspan="3" |(1.13-1.45) x In
|-
|Magnetic release characteristic
| colspan="3" |B:(3-5) x In, C:(5-10) x In, D:(10-20) x In
|-
|Electrical life
| colspan="3" |4,000 Cycles
|-
|Mechanical life
| colspan="3" |10,000 Cycles
|-
|Contact position indicator
| colspan="3" |Yes
|-
|Ground fault indicator
| colspan="3" |Yes
|-
|Protection degree
| colspan="3" |IP20
|-
|Ambient temperature
| colspan="3" |-25℃ to +55℃, Max.95% humidity
|-
|Terminal connection type
| colspan="3" |Cable/Pin-type busbar
|-
|Max. terminal size for cable
| colspan="3" |25mm2
|-
|Max. tightening torque
| colspan="3" |2.5N.m
|-
|Installation
| colspan="3" |Mounting on 35mm DIN rail
|-
|Connection
| colspan="3" |From top
|}





Latest revision as of 16:04, 3 November 2025

RCBO device

An RCBO (Residual Current Circuit Breaker with Overcurrent protection) is a single electrical safety device that combines the functions of a Residual Current Device (RCD) and a Miniature Circuit Breaker (MCB). It protects circuits from two types of electrical faults: earth leakage currents (which RCDs protect against) and overcurrents (like overloads and short circuits, which MCBs protect against). If the household already does not posses a seperate RCD, this device allows to speed up the charger installation with a combined device  to safely operate the EV charger. 1 phase and 3 phase versions available.

Datasheet

EKL-63 RCBO

Certificates

CE and CB

Technical data

Standard IEC/EN61009-1
Protection Ground fault, Overcurrent and short circuit
Type of trip Ground fault: Electronic
Overload and short circuit: Thermo-magnetic
Type of protection (electric leakage) AC, A, S
No. of poles 1P+N 3module, 3P+N 5 module, N line with disconnected
Rated current In 6,10,16,20,25,32,40,50,63A
Rated voltage Ue 1P+N:230/240V~, 3P+N:400/415V~
Rated frequency 50/60Hz
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤50A),10In (In>50A)
Rated breaking capacity EKL5-63: 6,000A, EKL5-63H: 10,000A
Energy limiting class 3
Rated impulse withstand voltage (1.2/50) Uimp 4,000V
Dielectric test voltage at ind. Freq. for 1min 2kV
Thermal release characteristic (1.13-1.45) x In
Magnetic release characteristic B:(3-5) x In, C:(5-10) x In, D:(10-20) x In
Electrical life 4,000 Cycles
Mechanical life 10,000 Cycles
Contact position indicator Yes
Ground fault indicator Yes
Protection degree IP20
Ambient temperature -25℃ to +55℃, Max.95% humidity
Terminal connection type Cable/Pin-type busbar
Max. terminal size for cable 25mm2
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top