Difference between revisions of "PEN fault protection"

From Wiki
(Added approximate contents)
Line 2: Line 2:
  
  
PEN fault protection works by measuring current falling on PE wire.
+
PEN fault protection works by measuring current flowing in PE wire.
  
 
If it reaches or goes over 20mA, product turns the relays OFF.
 
If it reaches or goes over 20mA, product turns the relays OFF.
  
==CT CLAMP WIRING==
+
==PEN CT WIRING==
  
  
Line 13: Line 13:
 
Product has integrated PEN fault protection.
 
Product has integrated PEN fault protection.
  
In order to receive this functionality it is required to clamp internal current transformer onto PE cable as shown in the illustration above.
+
In order to receive this functionality it is required to pass the PE cable through the internal current transformer.
 +
CT shall be wired in terminal marked "PEN"
  
 
== CONFIGURATION OF PEN FAULT PROTECTION ==
 
== CONFIGURATION OF PEN FAULT PROTECTION ==

Revision as of 12:47, 28 June 2023

BRIEF DESCRIPTION

PEN fault protection works by measuring current flowing in PE wire.

If it reaches or goes over 20mA, product turns the relays OFF.

PEN CT WIRING

Wiring CT.png

Product has integrated PEN fault protection.

In order to receive this functionality it is required to pass the PE cable through the internal current transformer. CT shall be wired in terminal marked "PEN"

CONFIGURATION OF PEN FAULT PROTECTION

In order to enable PEN fault protection in your device, please follow these steps:

  • Power ON your charging station
  • Pair (if was not paired before)
  • Enter Main settings in mobile application
  • Enter Installer menu by typing in the Installer code
  • Scroll to PME FAULT DETECTION section
  • Enable PEN protection with the slider
PEN Fault settingsmarked.png