Here you can find information about '''Suggested configuration of 22 kW power TeltoCharge installer menu''' parameters according to your '''electrical grid'''.
 +
<br>
 +
  <h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">3 phase (3L+N+PE) | voltage between L-N 230V ± 10% | L-L 400V ± 10%</h2>
 +
  <ul style="list-style-type: none; margin: 0; padding: 0;">
 +
 
 +
<h2 style="color: #4a4a4a; font-size: 24px; font-weight: bold; margin-bottom: 10px;">Suggested installer menu configuration guide</h2>
 +
  <ul style="list-style-type: none; margin: 0; padding: 0;">
 +
Follow these steps to get started with TeltoCharge in a '''maximum''' 22 kW power:
 +
<br>
 +
 
 +
{| class="wikitable" style="text-align: center; border: 1px solid #0054A6; font-family: arial, sans-serif; width: 60%;"
 +
|-
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Option number in installer
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Installer menu parameter name
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 4px;" | Suggested value to set
 +
! style="background-color: #0054A6; color:#FFFFFF; padding: 8px;" | Link to description of parameter
 +
|-
 +
| style="padding: 8px;" | 01
 +
| style="padding: 8px;" | '''Max power from grid'''
 +
| style="padding: 8px;" | 32 A
 +
| style="padding: 8px;" | [[Max power from grid]]
 +
|-
 +
| style="padding: 8px;" | 02
 +
| style="padding: 8px;" | '''Supply voltage '''
 +
| style="padding: 20px;" | 230 V
 +
| style="padding: 8px;" | [[Supply voltage]]
 +
|-
 +
| style="padding: 8px;" | 03
 +
| style="padding: 8px;" | '''Upper voltage tolerance'''
 +
| style="padding: 8px;" | 10 %
 +
| style="padding: 8px;" | [[Upper voltage tolerance]]
 +
 
 +
|-
 +
| style="padding: 8px;" | 04
 +
| style="padding: 8px;" | '''Lower voltage tolerance'''
 +
| style="padding: 8px;" | 10 %
 +
| style="padding: 8px;" | [[Lower voltage tolerance]]
 +
 
 +
|-
 +
| style="padding: 8px;" | 05
 +
| style="padding: 8px;" | '''Phase priority'''
 +
| style="padding: 8px;" | L1
 +
| style="padding: 8px;" | [[Phase priority]]
 +
|-
 +
| style="padding: 8px;" | 06
 +
| style="padding: 8px;" | '''Difference between phases'''
 +
| style="padding: 8px;" | 180 °
 +
| style="padding: 8px;" | [[Difference between phases]]
 +
|-
 +
| style="padding: 8px;" | 07
 +
| style="padding: 8px;" | '''Use neutral as phase'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Use neutral as phase]]
 +
|-
 +
| style="padding: 8px;" | 08
 +
| style="padding: 8px;" | '''Use data from energy meter'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Use data from energy meter]]
 +
|-
 +
| style="padding: 8px;" | 09
 +
| style="padding: 8px;" | '''kWh meter address'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - follow link on the right.''
 +
| style="padding: 8px;" rowspan="5" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 +
|-
 +
| style="padding: 8px;" | 10
 +
| style="padding: 8px;" | '''Energy meter type'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
|-
 +
| style="padding: 8px;" | 11
 +
| style="padding: 8px;" | '''RS-485 baudrate'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 12
 +
| style="padding: 8px;" | '''RS-485 parity'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 13
 +
| style="padding: 8px;" | '''RS-485 stop bit'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
|-
 +
| style="padding: 8px;" | 14
 +
| style="padding: 8px;" | '''Dynamic load balancing'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Dynamic Load Balancing]]
 +
|-
 +
| style="padding: 8px;" | 15
 +
| style="padding: 8px;" | '''Use preferred phase'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.'''
 +
| style="padding: 8px;" | [[Use prefered phase]]
 +
|-
 +
| style="padding: 8px;" | 16
 +
| style="padding: 8px;" | '''Energy meter address'''
 +
| style="padding: 8px;" | '''Not needed to adjust if Dynamic load balancing is OFF.''' <br> ''If it's ON - you must follow link on the right.''
 +
| style="padding: 8px;" | [https://wiki.teltonika-energy.com/view/Smart_energy_meters#TeltoCharge_supported_smart_energy_meters Choose your Smart energy meter and its parameters]
 +
|-
 +
| style="padding: 8px;" | 17
 +
| style="padding: 8px;" | '''Allow simplified charging sequence'''
 +
| style="padding: 8px;" | OFF
 +
| style="padding: 8px;" | [[Allow simplified charging sequence]]
 +
|-
 +
| style="padding: 8px;" | 18
 +
| style="padding: 8px;" | '''Charger location is ventilated'''
 +
| style="padding: 8px;" | OFF (if your TeltoCharge is inside the property)
 +
| style="padding: 8px;" | [[Charger location is ventilated]]
 +
|-
 +
| style="padding: 8px;" | 19
 +
| style="padding: 8px;" | '''Temperature warning'''
 +
| style="padding: 8px;" | 60 °C
 +
| style="padding: 8px;" | [[Temperature warning]]
 +
|}