Difference between revisions of "LED indicators"
Line 69: | Line 69: | ||
!F | !F | ||
!G | !G | ||
− | |||
|- | |- | ||
|[[File:TeltoCharge LEDS InputVoltageError.png|center|frameless]] | |[[File:TeltoCharge LEDS InputVoltageError.png|center|frameless]] | ||
Line 78: | Line 77: | ||
|[[File:TeltoCharge LEDS OtherErrors.png|center|frameless]] | |[[File:TeltoCharge LEDS OtherErrors.png|center|frameless]] | ||
|[[File:TeltoCharge LEDS FaultyConnection.gif|center|frameless]] | |[[File:TeltoCharge LEDS FaultyConnection.gif|center|frameless]] | ||
− | |||
|- | |- | ||
|Input voltage error. | |Input voltage error. | ||
Line 87: | Line 85: | ||
|Internal errors. | |Internal errors. | ||
|Faulty connection to EV. | |Faulty connection to EV. | ||
− | |||
|- | |- | ||
|Overvoltage; | |Overvoltage; | ||
Line 105: | Line 102: | ||
| -12V; | | -12V; | ||
|CP fail | |CP fail | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | colspan=" | + | | colspan="7" |<center><big>Troubleshooting</big></center> |
|- | |- | ||
| | | | ||
Line 141: | Line 131: | ||
| | | | ||
*Try reconnect charging cable from the EV side. There might be control pilot communication problem which can occur with different EV models. | *Try reconnect charging cable from the EV side. There might be control pilot communication problem which can occur with different EV models. | ||
− | | | + | |- |
+ | | colspan="7" |<center><big>If issues still persists, report it via VIP helpdesk or your sales manager. ('''Note:''' please provide as much information as you can about your issue (photos, videos, etc..) this helps to solve it faster.</big></center> | ||
+ | |- | ||
+ | |} | ||
+ | |||
+ | ===ORANGE LED indicators (warnings)=== | ||
+ | {| class="wikitable" | ||
+ | |+ | ||
+ | !A | ||
+ | !B | ||
+ | !C | ||
+ | !D | ||
+ | !E | ||
+ | !F | ||
+ | !G | ||
+ | !H | ||
+ | !I | ||
+ | !J | ||
+ | !K | ||
+ | !L | ||
+ | !M | ||
+ | |- | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |[[File:Orange_LED_warning_LED.png|center|frameless|alt=|150x150px]] | ||
+ | |- | ||
+ | |Simple CP detected | ||
+ | |Temperature warning | ||
+ | |Ventilation required | ||
+ | |RTC time lost | ||
+ | |Simplified CP denied | ||
+ | |D state denied | ||
+ | |CT clamps not calibrated | ||
+ | |Sensors not calibrated | ||
+ | |Energy meter comm error | ||
+ | |NFC init error | ||
+ | |Low battery voltage | ||
+ | |Emeter wrong type | ||
+ | |Emeter unidetified | ||
+ | |- | ||
+ | |Connected EV uses Simplified charging sequence. Charging power is limited to1 Phase 10 A; | ||
+ | |||
+ | |Temperature higher than warning limit, current throttling | ||
+ | is present. | ||
− | + | |EV requiring ventilation | |
− | + | |EVSE date and time lost | |
− | + | |Simplified CP detected and not allowed | |
+ | |EV requiring ventilation but charging location is not ventilated | ||
+ | |CT clamps are not calibrated | ||
+ | |Sensors were not calibrated during HW configuration | ||
+ | |Energy meter communication error | ||
+ | |NFC initialization error | ||
+ | |Low battery voltage EVSE (RTC) | ||
+ | |Energy meter configuration mismatch | ||
+ | |Energy meter type unidentified | ||
|- | |- | ||
− | | colspan=" | + | | colspan="13" |<center><big>Troubleshooting</big></center> |
+ | |- | ||
+ | | | ||
+ | Connected EV uses Simplified charging sequence. Charging power is limited. In installer menu option „Simplified charging sequence“ must be turned ON. | ||
+ | | | ||
+ | |||
+ | | | ||
+ | Check if Charging location is sufficiently ventilated | ||
+ | | | ||
+ | Check EVSE RTC coin battery (CR 1220) | ||
+ | | | ||
+ | Connected EV uses Simplified charging sequence. Simplified CP charging is disabled in Installer menu. | ||
+ | | | ||
+ | EV requiring ventilation, but Charging location is specified as not ventilated in Installer menu. | ||
+ | | | ||
+ | N/A | ||
+ | | | ||
+ | Contact support. | ||
+ | | | ||
+ | Check RS485 connection with external meter. Inspect cable. Check if meter is working. Make sure devices are configutated properly. | ||
+ | | | ||
+ | Reboot charger and check if the issue remains. | ||
+ | | | ||
+ | Check EVSE RTC coin battery (CR 1220). | ||
+ | | | ||
+ | Connected Energy meter and configured Energy meter type in Installer menu are different. | ||
| | | | ||
+ | Unknown device detected. Check if the energy meter is compatible.| | ||
+ | |- | ||
+ | | colspan="13" |<center><big>If issues still persists, report it via VIP helpdesk or your sales manager. ('''Note:''' please provide as much information as you can about your issue (photos, videos, etc..) this helps to solve it faster.</big></center> | ||
+ | |- | ||
|} | |} | ||
[[Category: Installation]] | [[Category: Installation]] |
Revision as of 12:48, 3 January 2023
A | B | C | D | E | F | G | H | I | J | K | L | M |
---|---|---|---|---|---|---|---|---|---|---|---|---|
White LED‘s rolling from the bottom to the top – shows that TeltoCharge is booting up | White pulsing LED‘s – shows that TeltoCharge is in standby mode and waiting for action | Yellow pulsing LED‘s – shows that TeltoCharge is in standby mode with default settings. | Yellow LED‘s on – TeltoCharge is not charging, simplified charging sequence is required. | Blue LED‘s lights up from the middle – TeltoCharge do not require permission, it is waiting for EV to initiate charging process (go to state C). | Blue LED‘s pulsing – permission to charge is not granted. TeltoCharge requires authorization. | Four middle blue LED’s pulsing – TeltoCharge waiting to add new NFC card | Green LED‘s pulsing - Initialisation of charging. | Green LED‘s rolling upwards from the bottom – TeltoCharge is in charging process. | Green LED‘s on – TeltoCharge finished charging. | Purple LED‘s on – TeltoCharge requires ventilation (charging is done in state D). | Red four middle LED's - NFC/RFID card declined from the server. | Green four middle LED's - NFC/RFID card accepted from the server. |
Open installer menu via Teltonika Energy app, set and save settings. | Open installer menu via Teltonika Energy app and select to allow simplified charging sequence | Authorize yourself with app or NFC card. | Open installer menu via Teltonika Energy app and select that charging location is ventilated. To select that charger must be installed in ventilated location. | Check if NFC/RFID card is in a server cards whitelist. |
RED LED indicators (errors)
A | B | C | D | E | F | G |
---|---|---|---|---|---|---|
Input voltage error. | Output voltage/current error. | Current leakage detected. | Connectivity error. | Temperature error. | Internal errors. | Faulty connection to EV. |
Overvoltage;
Undervoltage; Wrong wiring. |
Overvoltage;
Undervoltage; Output current. |
Current leakage detected | Cable lock;
PP fail; Car diode. |
Temperature reached 85°C | -12V; | CP fail |
|
|
|
|
|
|
|
ORANGE LED indicators (warnings)
A | B | C | D | E | F | G | H | I | J | K | L | M |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Simple CP detected | Temperature warning | Ventilation required | RTC time lost | Simplified CP denied | D state denied | CT clamps not calibrated | Sensors not calibrated | Energy meter comm error | NFC init error | Low battery voltage | Emeter wrong type | Emeter unidetified |
Connected EV uses Simplified charging sequence. Charging power is limited to1 Phase 10 A; | Temperature higher than warning limit, current throttling
is present. |
EV requiring ventilation | EVSE date and time lost | Simplified CP detected and not allowed | EV requiring ventilation but charging location is not ventilated | CT clamps are not calibrated | Sensors were not calibrated during HW configuration | Energy meter communication error | NFC initialization error | Low battery voltage EVSE (RTC) | Energy meter configuration mismatch | Energy meter type unidentified |
Connected EV uses Simplified charging sequence. Charging power is limited. In installer menu option „Simplified charging sequence“ must be turned ON. |
Check if Charging location is sufficiently ventilated |
Check EVSE RTC coin battery (CR 1220) |
Connected EV uses Simplified charging sequence. Simplified CP charging is disabled in Installer menu. |
EV requiring ventilation, but Charging location is specified as not ventilated in Installer menu. |
N/A |
Contact support. |
Check RS485 connection with external meter. Inspect cable. Check if meter is working. Make sure devices are configutated properly. |
Reboot charger and check if the issue remains. |
Check EVSE RTC coin battery (CR 1220). |
Connected Energy meter and configured Energy meter type in Installer menu are different. |
Unknown device detected. Check if the energy meter is compatible.| | |