{| class="wikitable"
|No.
|'''Question'''
|'''Answer'''
|-
|1.
|How TeltoCharge sets maximum charging power when 3-phase charging is enabled?
|TeltoCharge checks which phase is loaded most, measures how much free current is available, and sets that current.
|-
|2.
|Can I use simplified charging sequence with Dynamic load balancing.
|Yes, there is possibility to use both features together, but there are some limitations which are regulated by the standard (IEC 61851-1 / SAE J1772):

# Maximum charging current is only 10 Ampers.
# Possible to use only 1-phase charging.
|-
|3.
|Can I use 3-phase smart meter for single phase charger?
|No, there is no possibility to use 1-phase charger with 3-phase smart meter.
|-
|4.
|Does Load balancing limits Dynamic load balancing?
|Yes, if dynamic load balancing is enabled and user want to achieve maximum charging power without any other limitations except form smart energy meter. [https://wiki.teltonika-energy.com/view/Functionalities#Load_balancing Load balancing] should be set to the maximum value.
|-
|5.
|If "''use preferred phase''" is enabled, can charger automatically change phase?
|Yes, If TeltoCharge detects that prioritized phase is loaded and the maximum current it can give is 7 or less ampers, charger will make a check If other phases are loaded less:

* If there is other phase which is loaded less, charger will chnage charging phase.
* If other two phases ar loaded charger will stop charging process.
|-
|6.
|How TeltoCharge prioritizes phases when phase priority is disabled, TeltoChagre connected to three phases and three phase charging is disabled?
|Charger checks which phase is least loaded and selects that phase as a charging phase. If during charging process any of other two phases load decreases and the maximum available current will be 5 ampers higher then the charging phase, TeltoCharge will change charging phase to least loaded.
|}